Permit Number: T12CM00027
Parcel: 106070980

Review Status: Completed

Review Details: COMMERCIAL - NEW

Permit Number - T12CM00027
Review Name: COMMERCIAL - NEW
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
01/10/2012 MARTIN BROWN FIRE REVIEW Denied Per 2006 IFC, section 903.2.2, E buildings require sprinklers unless exterior door lead directly to outside. The presence of a roof over the door eliminates this exception to the fire sprinkler requirement. Either relocate doors, add an additional door, eliminate roof, or add fire sprinklers.
01/12/2012 RONALD BROWN BUILDING-COMMERCIAL REVIEW Denied 1. As per COT code amendent 903.2.2, all group "E" occupancies shall have a sprinkler system unless each classromm has an exit directly to the outside. Building 17, North does not meet this requirement with exits under roof and down a entry corridor.
2. Please provide a written summary of all deferred submittals send to the building official, Mr. Ron Boose, for the purpose of assessing additional review fees.
END OF REVIEW
01/24/2012 LEERAY HANLY PLUMBING-COMMERCIAL REVIEW Denied 1. Include in your material schedule insulation requirements for domestic water, hydronic piping and condensate piping. Reference: Service water insulation 2006 IECC. 2. See detail six on sheet 2.0 Hot water piping shall correspond to the left hand side of the fixture.
01/24/2012 RAY MAJUTA ELECTRICAL-COMMERCIAL REVIEW Approved
02/01/2012 ROBERT SHERRY WATER REVIEW Approved
02/01/2012 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Approved
02/07/2012 GERRY KOZIOL WWM REVIEW Denied 1. WALTER DOUGLAS ELEM SCHOOL - CLASSRM BLDG #16 SOUTH BLDG - SCHOOL @SFR RATE

2. CONNECTING TO ON-SITE PRIVATE SEWER

3. NEED TO RELOCATE PRIVATE C.O. #1 FROM PUBLIC ROW TO SCHOOL PROPERTY PER PERMIT#PT12S00163

Final Status

Task End Date Reviewer's Name Type of Review Description
02/14/2012 CINDY AGUILAR OUT TO CUSTOMER Completed