Permit Review Detail
Review Status: Completed
Review Details: COMMERCIAL - NEW
Permit Number - T12CM00026
Review Name: COMMERCIAL - NEW
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 01/10/2012 | MARTIN BROWN | FIRE | REVIEW | Denied | Per 2006 IFC, section 903.2.2, E buildings require sprinklers unless exterior door lead directly to outside. The presence of a roof over the door eliminates this exception to the fire sprinkler requirement. Either relocate doors, add an additional door, eliminate roof, or add fire sprinklers. |
| 01/12/2012 | RONALD BROWN | BUILDING-COMMERCIAL | REVIEW | Denied | 1. As per COT code amendent 903.2.2, all group "E" occupancies shall have a sprinkler system unless each classromm has an exit directly to the outside. Building 17, North does not meet this requirement with exits under roof and down a entry corridor. 2. Please provide a written summary of all deferred submittals send to the building official, Mr. Ron Boose, for the purpose of assessing additional review fees. END OF REVIEW |
| 01/20/2012 | LEERAY HANLY | ELECTRICAL-COMMERCIAL | REVIEW | Approved | |
| 01/24/2012 | LEERAY HANLY | PLUMBING-COMMERCIAL | REVIEW | Denied | 2. How is the insulation requirements for domestic water systems being met? Reference: 2006 IECC. Include in your materials schedule, insulation requirements for domestic water piping,condensate piping, and hydronic piping if applicable. 2. See detail six on sheet 2.0 Hot piping shall correspond to the left hand side of the fixture. |
| 02/01/2012 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Approved | |
| 02/01/2012 | ROBERT SHERRY | WATER | REVIEW | Approved | |
| 02/07/2012 | GERRY KOZIOL | WWM | REVIEW | Denied | 1. WALTER DOUGLAS ELEM SCHOOL - CLASSRM BLDG #17 NORTH BLDG - SCHOOL @SFR RATE 2. NEED TO RELOCATE PRIVATE C.O. #1 FROM PUBLIC ROW TO SCHOOL PROPERTY - CURRENTLY SHOWN ON BAKER & ASSOCIATES ENGINEERING DRAWING C1-1 |
Final Status
| Task End Date | Reviewer's Name | Type of Review | Description |
|---|---|---|---|
| 02/14/2012 | CINDY AGUILAR | OUT TO CUSTOMER | Completed |