Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

Permit Number: T12CM00022
Parcel: 11616287A

Address:
845 N MAIN AV

Review Status: Completed

Review Details: COMMERCIAL - TI

Permit Number - T12CM00022
Review Name: COMMERCIAL - TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
02/02/2012 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Denied 1. Verify the floor sink for the ice maker is located in a readily accessible location. Reference: Section 802.3, IPC 2006.
2. Provide the gas loads and developed pipe lengths for the new and relocated cooking equipment under the existing Type I hood. Reference: Section 402.2, IFGC 2006.
02/02/2012 ROBERT SHERRY WATER REVIEW Approved
02/02/2012 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Denied 1. Provide manufacturer's equipment and balancing data for the new Type I hood. Reference: Sections 301.6, 507.1, and 508.1, IMC 2006.
2. Revise the equipment layout under the existing hood. Hood canopies shall extend at least 6" horizontally on all open sides beyond the edge of the top horizontal surface of the appliances under the hood. Reference: Section 507.12, IMC 2006.
3. Revise the size of the grease ducts serving the new Type I hood to provide a minimum velocity of 1500 feet per minute (18"x16" @ 2900 CFM = 1450 FPM). Reference: Section 506.3.4, IMC 2006, as amended by the City of Tucson.
4. Provide information to show that the operation of the new Type I hood and the two hood exhaust fans complies with Section 507.2.1.1, IMC 2006.
5. Provide structural calculations and details to show that the new Type I hood is supported from the building structure in accordance with Section 507.6, IMC 2006. Reference: Section 302.1, IMC 2006.
6. Show that the new hood installation complies with Section 507.9, IMC 2006 for clearances (e.g. wall construction).