Permit Number: T12BU01060
Parcel: 99999999B

Review Status: Completed

Review Details: BILLBOARD - BLDG30days

Permit Number - T12BU01060
Review Name: BILLBOARD - BLDG30days
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
10/08/2012 GLENN MOYER ADMINISTRATIVE ADMIN REVIEW Denied BRC Comments

Below are comments for the required modification resubmittal for COT ID# 214
at 6501 South Nogales Highway (T12BU01060).

Sheet 1 of 2

1. In General Notes #9, delete "(G)" and "(X)" (these two subsections re
apron replacement and electrical replace ment are no longer applicable under
the revised resubmittal).

Sheet 2 of 2

1. In the boxed note on Exhibit 9, Section 2, delete "(G)" and "(X)" (these
two subsections re apron replacement and electrical replacement are no
longer applicable under the revised resubmittal).

2. Revise the East Face Elevation title so as to note that the west
elevation is same except for dimensions between uprights being reversed.

3. In fourth note of Scope of Work, add clarifying note that aprons are not
to be replaced or reinstalled at new location(as was done with catwalks and
safety cables).

4. In eighth note of Scope of Work, revise auger depth to match depiction
and note on the East Face Elevation.

5. In first note in Scope of work, add that electrical service and other
electrical parts to be removed as well (a further explanation may be added
that light fixtures, electrical service and other electrical parts are to be
reinstalled under separate electrical permit).

6. In Scope of Work, delete final note regarding reinstallation of light
fixtures

7. In Top View note, delete reference to the existing light fixtures being
reinstalled (again, a further explanation may be added that light fixtures
are to be reinstalled under separate electrical permit).
10/09/2012 LEERAY HANLY BUILDING-COMMERCIAL REVIEW Passed

Final Status

Task End Date Reviewer's Name Type of Review Description
10/09/2012 CINDY AGUILAR OUT TO CUSTOMER Completed