Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

Permit Number: T12BU01060
Parcel: 99999999B

Review Status: Completed

Review Details: BILLBOARD - BLDG30days

Permit Number - T12BU01060
Review Name: BILLBOARD - BLDG30days
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
09/11/2012 LEERAY HANLY BUILDING-COMMERCIAL REVIEW Needs Review
10/01/2012 GLENN MOYER ADMINISTRATIVE ADMIN REVIEW Denied BRC Comments

Below are comments for the required modification submittal for COT ID# 214
at 6501 South Nogales Highway (T12BU01060).

Sheet 1 of 2

1. In General Notes #9, delete "(Y)" (there is no "Y" in Exhibit 9, Section
2).

2. In General Notes #9, add "(B)" and "(F)" (for respective replacement of
stringers (apron) and angle clips as shown on Sheet 2).

3. Depict and identify the path of the relocated underground electrical
service on the aerial photograph underlay.

Sheet 2 of 2

1. In the boxed note on Exhibit 9, Section 2, delete "(Y)" (there is no "Y"
in Exhibit 9, Section 2).

2. In the boxed note on Exhibit 9, Section 2, add "(B)" and "(F)" (for
respective replacement of stringers (apron) and angle clips as shown on
Sheet 2).

3. Provide detail on the existing and any replacement for underground
electrical feed, including conduit material/size and trench dimensions.

4. The boxed note on Exhibit 9 includes Section 2(x), but the Scope of Work
does not list any electrical replacement work; clarify whether any
electrical parts are to be replaced.

5. Include all electrical removal and reinstallation/replacement work in
Scope of Work; clarify whether all electrical parts (other than the
underground feed) are to be relocated in their current configuration.

6. Provide standard electrical plan details, including light fixture
mounting, description of existing lamps, panel schedule, riser diagram, and
one-line diagram.

7. Add note that beam holes to be backfilled only with native earth removed
from holes.

8. The original engineered plan shows beam depth of 6'0"; use this as the
default beam depth (subject to field measurement upon excavation; the
depiction shows the beam depth as almost 8'0").

9. The plan specifies replacement of TEK screws, but it appears that there
are no existing TEK screws; delete the reference to TEK screws or be more
specific about the number and location of such existing and replacement
screws.

Final Status

Task End Date Reviewer's Name Type of Review Description
10/04/2012 FERNE RODRIGUEZ OUT TO CUSTOMER Completed