Permit Review Detail
Review Status: Completed
Review Details: POOL - COMM MODEL
Permit Number - T12BU00894
Review Name: POOL - COMM MODEL
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 07/26/2012 | ERIC NEWCOMB | BUILDING-COMMERCIAL | REVIEW | Approved | |
| 07/26/2012 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Approved | |
| 07/26/2012 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Denied | Provide calculations to show that the gas supply pipe to the pool heater is adequately sized. (The hotel design drawings showed a developed length of 182 feet from the meter to the pool heater.) |
| 07/26/2012 | JASON GREEN | ENGINEERING | REVIEW | Approved | |
| 07/26/2012 | RAY MAJUTA | ELECTRICAL-COMMERCIAL | REVIEW | Denied | Provide Panel schedule and loads including circuits for pool equipment. Provide specifications for motor and lights. Size and circuit branch circuits for pool equipment . Ray T majuta 7/26/2012 |
| 07/26/2012 | TERRY STEVENS | ZONING | REVIEW | Approved |