Permit Number: T12BU00894
Parcel: 12504079B

Review Status: Completed

Review Details: POOL - COMM MODEL

Permit Number - T12BU00894
Review Name: POOL - COMM MODEL
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
07/26/2012 ERIC NEWCOMB BUILDING-COMMERCIAL REVIEW Approved
07/26/2012 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Approved
07/26/2012 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Denied Provide calculations to show that the gas supply pipe to the pool heater is adequately sized. (The hotel design drawings showed a developed length of 182 feet from the meter to the pool heater.)
07/26/2012 JASON GREEN ENGINEERING REVIEW Approved
07/26/2012 RAY MAJUTA ELECTRICAL-COMMERCIAL REVIEW Denied Provide Panel schedule and loads including circuits for pool equipment.
Provide specifications for motor and lights.
Size and circuit branch circuits for pool equipment .

Ray T majuta
7/26/2012
07/26/2012 TERRY STEVENS ZONING REVIEW Approved