Review Date Reviewer's Name Type of Review Description Status Comments
07/12/2012 LEERAY HANLY BUILDING-COMMERCIAL REVIEW Needs Review
07/17/2012 GLENN MOYER ADMINISTRATIVE ADMIN REVIEW Denied BRC Comments

Below are comments for the electrical repair submittal for COT ID# 501 at
2501 North Oracle Road (T12BU00829).

Sheet 1 of 1

1. Provide correct aerial overlay parcel, billboard footprint, assessor
parcel number, legal description, location map and other applicable entries
or depictions for COT #501 (those shown are all for a billboard other than
COT #501).

2. Provide name of applicant/site plan preparer in title block.

Sheet 2 of 2

1. In South Face Sign Elevation, provide correct vertical measure of face
panel.

2. In South Face Sign Elevation, provide correct gauge for replacement
ballast wire (#8 is shown, contrary to the #18 stated elsewhere on plan
sheet).

3. In South Face Sign Elevation, delete reference to north face being
similar; either add north face elevation or add text specifying the
difference(s).

4. For incoming feed wire, show #12 being upgraded to #10, rather than #6;
#10 is the minimum needed to meet NEC for 30A service.

5. In Panel Schedule, provide correct volt-amps to reflect ballast input
power (rather than the rated lamp power alone).

6. Resolve conflict between One Line Diagram and Panel Schedule as to
lighting circuit breaker rating (20A vs. 15A).

7. In Scope of Work conform the ¾” EMT between the 122 Panel and first
junction box to the ½” EMT shown in the electrical riser diagrams; resolve
inconsistency between Scope of Work and electrical riser diagrams as to EMT
size between first and second junction boxes (use 1/2" EMT unless 3/4" is
necessary to meet NEC).

8. Add partial vicinity map and partial plan view.

9. Add note indicating that no junction boxes or other fixtures, where wire
connections are made, shall be added or replaced other than those shown on
plan.

Final Status

Task End Date Reviewer's Name Type of Review Description
08/21/2012 CINDY AGUILAR OUT TO CUSTOMER Completed