Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

PRO is currently experiencing an outage. Some documents and records may not be available on PRO momentarily. We apologize for the inconvenience and are working to restore full access.

Permit Number: T12BU00652
Parcel: 10601247B

Address:
215 E PRINCE RD

Review Status: Completed

Review Details: GRADING

Permit Number - T12BU00652
Review Name: GRADING
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
05/24/2012 ELEIBOL1 NPPO REVIEW Passed per Joe
05/24/2012 STEVE SHIELDS ZONING REVIEW Passed
05/25/2012 ELIZABETH LEIBOLD ENGINEERING REVIEW Approved

Final Status

Task End Date Reviewer's Name Type of Review Description
05/29/2012 CINDY AGUILAR OUT TO CUSTOMER Completed