Permit Number: T12BU00591
Parcel: 99999999B

Address:
1048 E 22ND ST

Review Status: Completed

Review Details: BILLBOARD - BLDG30days

Permit Number - T12BU00591
Review Name: BILLBOARD - BLDG30days
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
05/09/2012 LEERAY HANLY BUILDING-COMMERCIAL REVIEW Needs Review
06/05/2012 GLENN MOYER ADMINISTRATIVE ADMIN REVIEW Denied BRC Comments

Below are comments for the authorized repair submittal for COT ID# 62 at
1048 East 22nd Street (T12BU00591).

Sheet 1 of 1

1. Correct the Pima County Assessor Number in Billboard Notes and on aerial
overlay (the number was changed in March).

2. Correct the legal description to match the current parcel configuration.

3. Provide graphic depiction and legal description of any easement of
record or private agreement that pertains to the billboard, including areas
related to access and visibility.

4. In Billboard Note #9, conform the subsections provided with those shown
on Sheet 2 (Subsection 2(j) needs to be deleted; Subsection 2(g) needs to be
added; and the inclusion of other subsections may need to be clarified).

Sheet 2 of 2

1. In Plan View & Typical Section Thru Sign, indicate light fixture to be
removed and reinstalled (rather than to remain).

2. In Plan View & Typical Section Thru Sign, indicate metal face panel to
be removed and reinstalled or otherwise (rather than to remain).

3. Provide standard detail of spacers to be replaced (side view).

4. In Scope of Work, provide detail on metal face panel section work,
including number and full dimensions of each (length, width, depth, and
gauge), for both removal and reinstallation.

5. In Description of Existing Lamp, clarify which light fixtures the
existing lamp specifications apply to.

6. Delete reference to Exhibit 9, Section 2(j); COT ID# 62 is not one of
the nine eligible billboards listed.

7. Provide location and full detail for any walkaround proposed to be
replaced under Exhibit 9, Section 2(k) and include in Scope of Work (or
otherwise delete Section 2(k)).

8. Clarify the location and number of TEK screws to be replaced (in the
existing installation, such screws appear to be limited to the outside wood
sections).

Final Status

Task End Date Reviewer's Name Type of Review Description
08/21/2012 CINDY AGUILAR OUT TO CUSTOMER Completed