Permit Number: T12BU00590
Parcel: 10503034D

Address:
5115 N ORACLE RD

Review Status: Completed

Review Details: BILLBOARD - BLDG30days

Permit Number - T12BU00590
Review Name: BILLBOARD - BLDG30days
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
05/09/2012 LEERAY HANLY BUILDING-COMMERCIAL REVIEW Needs Review
05/24/2012 GLENN MOYER ADMINISTRATIVE ADMIN REVIEW Denied BRC Comments

Below are comments for the authorized repair submittal for COT ID# 482 at
5115 North Oracle Road (T12BU00590).

Sheet 1 of 2

1. In Billboard Notes, conform the sections of Exhibit 9 cited to those
cited on Sheet 2.

Sheet 2 of 2

1. Correct or clarify the height measurements (measurements of record are
in the range of 34.2 to 34.9 feet); show the height at the leading edges
rather than the rear edges, particularly here where the building conflicts
with one of the rear edge measurements.

Final Status

Task End Date Reviewer's Name Type of Review Description
05/25/2012 GERARDO BONILLA REJECT SHELF Completed