Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

Permit Number: T12BU00528
Parcel: 99999999B

Address:
1820 E AJO WY

Review Status: Completed

Review Details: BILLBOARD - BLDG30days

Permit Number - T12BU00528
Review Name: BILLBOARD - BLDG30days
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
07/26/2012 LEERAY HANLY BUILDING-COMMERCIAL REVIEW Needs Review
08/22/2012 GLENN MOYER ADMINISTRATIVE ADMIN REVIEW Denied BRC Comments

Below are comments for the authorized electrical repair resubmittal for COT
ID# 277 at 1820 East Ajo Way (T12BU00528).

Sheet 1 of 2

No comments.

Sheet 2 of 2

1. Comment #3 on the original submittal was not responded to regarding the
122 Panel Schedule; please cross out all but the two circuits provided with
this panel (there are no additional spaces).

2. The number of capacitor hours back up in the manufacturer's literature
appears to have been inadvertently changed from the 100 hours shown in the
original submittal to 0 hours in the resubmittal and needs to be corrected.


3. Comment #5 on the original submittal was not correctly responded to; in
the 122 Panel Schedule, the v-a entry for the lighting circuit remains
substantially understated and does not reflect two pair of VHO lamps being
powered by the two indicated ballasts [BRC calculation: 431 (WPR-931 input
power) x 2 x 1.25 = 1077.5 v-a].

4. In the Current Lamp Description, correct the wattage for the VHO lamps
(the wattage shown is for HO lamps) and the average rated life (the other
entries appear to be correct for the stated Sylvania lamp).

Final Status

Task End Date Reviewer's Name Type of Review Description
09/05/2012 CPIERCE1 REJECT SHELF Completed