Permit Number: T12BU00528
Parcel: 99999999B

Address:
1820 E AJO WY

Review Status: Completed

Review Details: BILLBOARD - BLDG30days

Permit Number - T12BU00528
Review Name: BILLBOARD - BLDG30days
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
05/02/2012 LEERAY HANLY BUILDING-COMMERCIAL REVIEW Needs Review
05/25/2012 GLENN MOYER ADMINISTRATIVE ADMIN REVIEW Denied BRC Comments

Below are comments for the authorized electrical repair submittal for COT
ID# 277 at 1820 East Ajo Way (T12BU00528).

Sheet 1 of 2

No comments.

Sheet 2 of 2

1. Indicate replacement of 206 panel that served COT #276 billboard with
basic service disconnecting means (switch) with a rating to match the 122
panel.

2. In New Electrical Riser Diagram, show the dimension for the new wood
pole height and footing depth more clearly associated with the pole
depiction (the pole appears to exceed the height dimension shown).

3. In Panel Schedule, delete "spaces" and cross out all but two circuits
(to match the 122 panel configuration).

4. Show east face light fixtures and associated conduit and wiring to be
removed (there is no existing east face to be illuminated and only the west
face is allowed under the Stipulation).

5. In Panel Schedule and other applicable depictions, delete east face
lighting circuit.

6. In Panel Schedule, revise the v-a entries for the west face lighting
circuit to correctly account for the ballast input for two dual lamp VHO
fixtures and the stated 125% load factor.

7. Indicate the specific EWZ series timer to be installed in 122 panel box.

8. In title block, indicate authorized electrical repair

Final Status

Task End Date Reviewer's Name Type of Review Description
07/24/2012 CINDY AGUILAR OUT TO CUSTOMER Completed