Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.

Permit Number: T12BU00348
Parcel: 14044007E

Review Status: Completed

Review Details: GRADING

Permit Number - T12BU00348
Review Name: GRADING
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
03/27/2012 MICHAEL ST. PAUL ZONING REVIEW Denied March 27, 2012

Development Services Department
Zoning Review Section

Michael St.Paul
Planning Technician

T12BU00348 Grading Plans for D08-0055

Address:
5300 East Los Reales Road

Comments:

1. The grading plan has been reviewed by Zoning Review Section but cannot approve the plan until it has been approved by the Engineering and Landscape Review Sections.

2. Please submit one copy of the approved and stamped Development Plan, Landscape, and NPPO plans with the next grading plan submittal.

3. Zoning will re-review the grading plan on the next submittal to ensure compliance with the approved development plan. Additional comments may be forthcoming.
04/05/2012 ELIZABETH LEIBOLD ENGINEERING REVIEW Denied DATE: April 5, 2010
TO: Carl Bueter, P.E., Cornerstone Environmental Group
SUBJECT: Los Reales Landfill Facility 1st Grading Plan submittal Engineering Review
LOCATION: Ward 5, Parcel 140-39-052C, 2850K
REVIEWER: Elizabeth Leibold
CASE NUMBER: D08-0055
ACTIVITY NUMBER: T12BU00348

SUMMARY: The grading permit application package was submitted for review. Planning & Development Services Department Engineering Division has reviewed the received items and does not recommend approval of the Grading Plan until the following comments are addressed. Floodplain use permit will be reviewed separately.

GRADING PLAN COMMENTS:
1) DS Sec.11-01: Address the following grading/swpp comments:
a. Clarify rip rap with filter fabric in legend on sheet 1.
b. Hills or depressions indicated on sheet C2 are not shown on other sheets - clarify and provide grading information.
c. Provide copy of geotechnical report and addenda in next submittal.
d. Consider revising Detail 1/C9 to clarify that stormwater runoff is not channeled along the front of the silt fence but allowed to pass through the fabric.
e. Clarify locations of silt fence and wattle on sheet C10.

For resubmittal, provide 2 copies of full set including revised grading plan sheets & revised SWPPP sheets, Geotechnical Report with addenda, and other documentation as needed, with response letter. If you have questions please email, or call me at 837-4934.

Elizabeth Leibold, P.E., CPM, CFM
Civil Engineer
Engineering Division
Planning & Development Services Department
04/06/2012 ANDREW CONNOR NPPO REVIEW Denied 1. Provide approved development plans for reference.

2. Ensure that all Engineering comments and concerns are addressed

3. Additional comments may apply

Final Status

Task End Date Reviewer's Name Type of Review Description
04/13/2012 FERNE RODRIGUEZ OUT TO CUSTOMER Completed