Permit Number: T12BU00195
Parcel: 99999999B

Address:
12501 E I10

Review Status: Completed

Review Details: BILLBOARD - BLDG30days

Permit Number - T12BU00195
Review Name: BILLBOARD - BLDG30days
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
02/10/2012 LEERAY HANLY BUILDING-COMMERCIAL REVIEW Needs Review
02/29/2012 GLENN MOYER ADMINISTRATIVE ADMIN REVIEW Denied BRC Comments

Below are comments for the authorized repair submittal for COT ID# 588 at
12501 East Interstate 10 (T12BU00195).

Sheet 1 of 1

1. Clarify location of Interstate 10 right-of-way line; the billboard
location depicted would appear to fall within the Interstate 10
right-of-way.

Sheet 2 of 2

1. In Typical Section Thru Sign, delete middle backrail; alternatively, add
depiction of middle backrail to Face Elevation and add separate points to
Scope of Work to address its removal and replacement.

2. In Scope of Work, the third and ninth points appear to relate to upper
backrail; indicate upper backrail or otherwise clarify which backrail is
being referred to in both points.

3. In Scope of Work, ninth and tenth points, clarify the number and lengths
of replacement backrail pieces.

4. In Scope of Work, add respective points on the removal and replacement
of the apron, indicating the number of pieces and the dimensional and
material detail (as has been typically provided).

5. Add note that finished height of wood section panels not to exceed
height of tallest wood pole.

6. Revise height of wood section panel depicted in Stringer & Attachment
Detail so as to not exceed height of pole shown.

7. In Face Elevation, pole diameters, heights, and separation distances
appear to be reversed for a rear elevation; revise so as to match a rear
elevation.

8. In Face Elevation, provide distances from outer pole centers to wood
section outer edges.

9. Clarify if pole diameters shown in Face Elevation and Pole Replacement
Detail are at base grade; if not, provide diameters at base grade.

10. Clarify if the depicted replacement pole depth below grade is same as
existing or, if not currently known, how such depth is to be determined.

11. Indicate the diameter of the footing hole for the replacement pole.

12 Add note that hole inspection is to be requested prior to replacement
pole installation and that replacement pole is to be available on site at
time of hole inspection.

13. Add note that backfill for pole replacement shall consist only of
native earth excavated in conjunction with removal of existing pole.

14. Add note indicating Stipulation allowance of two cumulative pole
replacements and that subject replacement is the first of the two allowed
(Exhibit 9, Sections 2(a) & 4(b)).

15. Provide specific provision in Stipulation under which scabs are
proposed to be replaced.

16. In Face Elevation, provide arrows indicating all scabs to be replaced.

Final Status

Task End Date Reviewer's Name Type of Review Description
11/19/2013 GERARDO BONILLA REJECT SHELF Completed