Permit Review Detail
Review Status: Completed
Review Details: PARKING PLAN
Permit Number - T11SA00168
Review Name: PARKING PLAN
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 05/12/2011 | GMOYER1 | ZONING | REVIEW | Approved | |
| 05/12/2011 | JOSE ORTIZ | DOT TRAFFIC | REVIEW | Completed | TDOT-Traffic has no objections to the proposed addition |
| 05/12/2011 | GMOYER1 | ZONING HC | REVIEW | Approved | |
| 05/16/2011 | RONALD BROWN | ADA | REVIEW | Approv-Cond | We have no problem with the overall parking reduction. Table 1106.1 requires 2% of the total parking spaces to be accessible. However there is a descrepancy in the Motor Vehicle and Parking tabulation of sheet T1.0 touting 16 accessible spaces provided. Two percent of 516 spaces provided equals 10 accessible spaces required, only 14 are shown on the site plan. Please either show me another 2 accessible spaces on the development plan or correct the provided number in the summary to 14. |
Final Status
| Task End Date | Reviewer's Name | Type of Review | Description |
|---|---|---|---|
| 05/18/2011 | SMONTES1 | APPROVAL SHELF | Completed |
| 05/18/2011 | SMONTES1 | OUT TO CUSTOMER | Completed |
| 05/18/2011 | SMONTES1 | REJECT SHELF | Completed |