Permit Number: T11PL00957
Parcel: 10818716A

Review Status: Completed

Review Details: PLUMBING

Permit Number - T11PL00957
Review Name: PLUMBING
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
09/21/2011 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Denied 1. The existing hydromechanical grease interceptor requires the use of readily accessible flow control devices for each connected fixtures. The floor sinks and the janitor's sink cannot be equipped with readily accessible flow control devices. Provide a hydromechanical grease interceptor with an integral flow control device or eliminate the existing hydromechanical grease interceptor.
2. A 2" horizontal drain is limited to 8 drainage fixture units.
09/27/2011 GBONILL1 WWM REVIEW Needs Review