Permit Review Detail
Review Status: Completed
Review Details: PLUMBING
Permit Number - T11PL00957
Review Name: PLUMBING
Review Status: Completed
Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
---|---|---|---|---|---|
09/21/2011 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Denied | 1. The existing hydromechanical grease interceptor requires the use of readily accessible flow control devices for each connected fixtures. The floor sinks and the janitor's sink cannot be equipped with readily accessible flow control devices. Provide a hydromechanical grease interceptor with an integral flow control device or eliminate the existing hydromechanical grease interceptor. 2. A 2" horizontal drain is limited to 8 drainage fixture units. |
09/27/2011 | GBONILL1 | WWM | REVIEW | Needs Review |