Permit Review Detail
Review Status: Completed
Review Details: C OF O
Permit Number - T11OT02027
Review Name: C OF O
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 11/14/2011 | DAVE MANN | FIRE | REVIEW | Denied | Fire Comments: The plans for this change of use must be sealed by the Architect. Only the registrant can change the plans per the Arizona State Board of Registration. The exits from the I-2 area do not comply with IFC Chapter 10. See IBC Sections 407.2, 407.3, and 407.4 for cooridor width for persons incapable of self preservation, also smoke partions and smoke separation of floors. Doors in the smoke partition must swing both ways; see IFC Section 1008. The alarm system must be modified to comply with IFC 907.2.6.2. The sprinkler system must comply with IFC 903.1.1. Verify quick reponse heads. |
| 11/15/2011 | LEERAY HANLY | BUILDING-COMMERCIAL | REVIEW | Denied | Doors in the smoke partition must swing both ways; see IFC Section 1008. Please clarify width of corrdors on plans for verification of adequate clear floor space in each smoke compartment. (IBC 407.4) |
| 11/22/2011 | MICHAEL ST. PAUL | ZONING | REVIEW | Approved |
Final Status
| Task End Date | Reviewer's Name | Type of Review | Description |
|---|---|---|---|
| 12/07/2011 | SUE REEVES | OUT TO CUSTOMER | Completed |
| 12/07/2011 | SUE REEVES | REJECT SHELF | Completed |