Permit Number - T11OT01762
Review Name: FLOODPLAIN
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
09/23/2011 ELIZABETH LEIBOLD ENGINEERING REVIEW Approv-Cond DATE: September 23, 2011
SUBJECT: Site Plan & Floodplain Use Permit Engineering Review for Detached Guest House Addition Structure
REVIEWER: Elizabeth Leibold
FLOOD INFO: 2277L, X Zone, West University Wash City of Tucson Flood Hazard area
ACTIVITY NUMBERS: T11OT01762, T10CM00520

SUMMARY: Planning & Development Services Department Engineering Division has completed a review of the received items. Site inspection occurred during storm event 19AUG11 to determine potential flooding areas. Engineering recommends approval of the Floodplain Use Permit application and guest house plans with the following conditions to be addressed during construction. The applicant is authorized to use a portion of City of Tucson jurisdictional floodplain, specifically described as:
995 N Jacobus Av (rear guest house to 620 E 1st St, Tucson AZ 85705, being a portion of Parcel 117-02-2910 of south half of lot 4 in Maps & Plat Bk1 pg19 Block 22, located within T14S R13E Section 12;
for the purpose of a lot improvement for guest house.
The applicant agrees to comply with City of Tucson Floodplain and Erosion Hazard, and if applicable, Watercourse Amenities, Safety and Habitat regulations, and are particularly bound by the conditions stated below. Violation of any of the conditions stated or referred to below, as determined by the City Engineer, shall be grounds for revocation of this permit. Responsibility for renewal of this permit, if necessary, is with the applicant. Issuance of this permit does not constitute a waiver of other requirements contained in the Tucson City Code, Land Use Code, or any other Federal, State, County, or local regulation. No use other than as permitted herein is allowed. Additional uses allowed under the City of Tucson Floodplain and Erosion Hazard Regulations require the issuance of an additional Floodplain Use Permit.

FLOODPLAIN USE PERMIT CONDITIONS:
The following 11 conditions apply to permits T11OT01762 & T10CM00520:
1) For a PDSD Engineering Inspection, call IVR (740-6970), or contact PDSD Engineering at 837-4991, or schedule inspections online at: http://www.ci.tucson.az.us/dsd/Online_Services/Online_Permits/online_permits.html
2) Floodplain Use Permit & plans shall be kept in readily accessible location on site at all times.
3) No disturbance other than the area within the lot and as shown on the approved plans.
4) Construction vehicles and materials shall not be stockpiled over sewer infrastructure in alley, or obstruct traffic within alleys or public streets.
5) Minimum new FFE elev 101.9 shown on page 3 of Drainage Statement Justin Turner P.E., sealed 8-29-11.
6) Within 5 (five) days of issuance of this permit, and through completion of the project, notification must be posted and maintained in a conspicuous place on the job site stating "CONSTRUCTION PROCEEDING UNDER REQUIREMENTS OF CITY OF TUCSON FLOODPLAIN USE PERMIT # T11OT01762. FOR INFORMATION PLEASE CALL 791-5550."
7) Except as approved by the City Engineer prior to the start of construction, development under this permit shall not obstruct, retard or divert the existing flow of floodwaters from or to adjacent properties.
8) This permit becomes invalid and is subject to additional floodplain review, if any required development permit changes the configuration of the improvement, or, if there is any further disturbance within the floodplain other than that outlined in this application. This floodplain use permit may be subject to conditions or restrictions designed to reduce or mitigate the potential damage or hazard to life or property resulting from development within the regulatory floodplain, floodway or erosion hazard areas as determined by the project engineer and accepted by the City of Tucson and PCRFCD.
9) See also associated permit: T10CM00520.
10) EXPIRATION DATE: Month: 9 Day: 26 Year: 2013
11) This Floodplain Use Permit will be automatically revoked and becomes invalid for non-compliance to conditions set forth in this permit. Also, this permit will expire 2 years from its date of issue. Renewal of this permit will require a new application, review and approval of that application by the City of Tucson, Planning & Development Services Department, Engineering Division.

If you have any further questions, you may contact me at 837-4934.

Elizabeth Leibold, P.E., CPM, CFM
Civil Engineer
Engineering Division
Planning & Development Services Department