Permit Review Detail
Review Status: Completed
Review Details: FLOODPLAIN
Permit Number - T11OT01189
Review Name: FLOODPLAIN
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 06/30/2011 | ELIZABETH EBERBACH | ENGINEERING | REVIEW | Approved | FLOODPLAIN USE PERMIT: T11OT01189 PROJECT ADDRESS: 2608 N Sahuara Pl, Tucson Arizona 85712 PROPERTY OWNER: Cornerstone Homes AZ LLC The applicant is authorized to use a portion of City of Tucson jurisdictional floodplain, specifically described as: 2608 N Sahuara Pl, Tucson AZ 85712, being a portion of Parcel 110-16-2310 of BACH PROPERTY LOT 7, located within T13S R14E Section 36; for the purpose of a subdivision lot improvement. The applicant agrees to comply with City of Tucson Floodplain and Erosion Hazard, and if applicable, Watercourse Amenities, Safety and Habitat regulations, and are particularly bound by the conditions stated below. Violation of any of the conditions stated or referred to below, as determined by the City Engineer, shall be grounds for revocation of this permit. Responsibility for renewal of this permit, if necessary, is with the applicant. Issuance of this permit does not constitute a waiver of other requirements contained in the Tucson City Code, Land Use Code, or any other Federal, State, County, or local regulation. No use other than as permitted herein is allowed. Additional uses allowed under the City of Tucson Floodplain and Erosion Hazard Regulations require the issuance of an additional Floodplain Use Permit. The following 11 conditions apply to permit T11OT01189: 1) For a PDSD Engineering Inspection, call IVR (740-6970), or contact PDSD Engineering at 837-4991, or schedule inspections online at: http://www.ci.tucson.az.us/dsd/Online_Services/Online_Permits/online_permits.html 2) If rear wall is built, at-grade wall openings will be needed & inspected by PDSD Engineering. 3) Floodplain Use Permit & plans shall be kept in readily accessible location on site at all times. 4) No disturbance other than the area within the lot and as shown on the approved plans. 5) PDSD Engineering Inspections are required prior to final floodplain inspection. 6) From FEMA data BFE = 2467.31 NAVD88. Minimum PAD elevation per plat = 2474.00. 7) Submit Elevation Certifications by a Land Surveyor registered in Arizona for the pad elevation (prior to pouring slab), and later for finished construction. PDSD Engineering has the preliminary elevation certificate filled out for the RLS to use, as needed. First elevation certificate must be submitted prior to pouring concrete slab to assure minimum height is achieved. Concrete slab may not be poured until PDSD Engineering accepts first elevation certificate. An additional El Cert is needed for finished construction. Assure the lowest elevation of the utility equipment to service the building is provided in C2e) and E4 on finished construction el cert. Notations should be added to clarify type of equipment and location. 8) Within 5 (five) days of issuance of this permit, and through completion of the project, notification must be posted and maintained in a conspicuous place on the job site stating "CONSTRUCTION PROCEEDING UNDER REQUIREMENTS OF CITY OF TUCSON FLOODPLAIN USE PERMIT # T11OT01189. FOR INFORMATION PLEASE CALL 791-5550." 9) Except as approved by the City Engineer prior to the start of construction, development under this permit shall not obstruct, retard or divert the existing flow of floodwaters from or to adjacent properties. 10) This permit becomes invalid and is subject to additional floodplain review, if any required development permit changes the configuration of the improvement, or, if there is any further disturbance within the floodplain other than that outlined in this application. This floodplain use permit may be subject to conditions or restrictions designed to reduce or mitigate the potential damage or hazard to life or property resulting from development within the regulatory floodplain, floodway or erosion hazard areas as determined by the project engineer and accepted by the City of Tucson and PCRFCD. 11) See also associated permit: T11CM01883. This Floodplain Use Permit will be automatically revoked and becomes invalid for non-compliance to conditions set forth in this permit. Also, this permit will expire 2 years from its date of issue. Renewal of this permit will require a new application, review and approval of that application by the City of Tucson, Planning & Development Services Department, Engineering Division. (EXPIRATION DATE) Month: 6 Day: 30 Year: 2013 APPLICANT: JACA Design LLC ADDRESS: PO Box 1131, Tucson AZ 85704 PHONE: (520) 808-4052 OWNER: Cornerstone Homes AZ LLC, (520) 795-7700 SIGNATURE OF APPLICANT DATE The applicant is authorized by the City Engineer to receive a floodplain use permit subject to the above referenced conditions and restrictions. |
Final Status
| Task End Date | Reviewer's Name | Type of Review | Description |
|---|---|---|---|
| 07/06/2011 | CPIERCE1 | OUT TO CUSTOMER | Completed |