Permit Number: T11OT00447
Parcel: 110120960

Address:
5301 E GRANT RD

Review Status: Completed

Review Details: OTHER - BLDG ONLY

Permit Number - T11OT00447
Review Name: OTHER - BLDG ONLY
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
03/31/2011 LEERAY HANLY BUILDING-COMMERCIAL REVIEW Denied Folder 1 ED Stat Lab. Electrical pages 3.1 & 3.2 are copies of pp M2.1 & M2.1. Where are electrical specifications?

Folder 4 for Pediatrics ICU AHU VFD upgrade has errors on the electrical pages. One lines for vfd connections violate code.

Folder 7 Cold Water Loop Connection has no files

Folder 10 MDF IDF Room upgrades. PP S 1.1 shows structual modifications to the roof. Registered Plant permits do not allow for structural modifications to load bearing structures.