Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.
Permit Review Detail
Review Status: Completed
Review Details: OTHER - BLDG ONLY
Permit Number - T11OT00447
Review Name: OTHER - BLDG ONLY
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 03/31/2011 | LEERAY HANLY | BUILDING-COMMERCIAL | REVIEW | Denied | Folder 1 ED Stat Lab. Electrical pages 3.1 & 3.2 are copies of pp M2.1 & M2.1. Where are electrical specifications? Folder 4 for Pediatrics ICU AHU VFD upgrade has errors on the electrical pages. One lines for vfd connections violate code. Folder 7 Cold Water Loop Connection has no files Folder 10 MDF IDF Room upgrades. PP S 1.1 shows structual modifications to the roof. Registered Plant permits do not allow for structural modifications to load bearing structures. |