Permit Number: T11OT00034
Parcel: 211350170

Review Status: Active

Review Details: FLOODPLAIN

Permit Number - T11OT00034
Review Name: FLOODPLAIN
Review Status: Active
Review Date Reviewer's Name Type of Review Description Status Comments
02/04/2011 ELIZABETH EBERBACH ENGINEERING REVIEW Approved DATE: February 4, 2011
TO: Peter Abraham, P.E., Tucson Water, 310 West Alameda, Tucson Arizona 85747
SUBJECT: Tucson Water Southern Avra Valley Storage And Recovery Project (SAVSARP) Phase 1 Well SA-009A Engineering Review
ADDRESS: 2990 S Sandario Rd
LOCATION: T14S, R11E, Section 28
REVIEWER: Elizabeth Leibold, P.E.
FLOODPLAIN INFO: FIRM Panel: 040192200K (effective date 2/8/99), SFHA zone: A01
ACTIVITY NUMBERS: T11BU00019 / T11OT00034

SUMMARY: PDSD Engineering Division has reviewed the plan set and recommends approval of floodplain use permit and grading permit. Drainage report was reviewed for Tucson Water SAVSARP Well SA-009A only.

GRADING PERMIT CONDITIONS:
1) The following conditions apply to grading permit T11BU00019:
a) This permit is for the initial phase of the Tucson Water SAVSARP well improvements SA-009A phase 1 only.
b) The Southern Avra Valley Storage And Recovery Project (SAVSARP) Well SA-009A Phase 1 plans - Tucson Water Plan No.1-015-2010 (SA-009A) and specifications are a part of the grading permit. See also Floodplain Analysis Summary Report for Southern Avra Valley Storage and Recovery Project (SAVSARP) Planned Recovery-Well Pad Sites by TetraTech dated December 9, 2009, sealed 12/09/09 Michael Zeller, P.E.
c) Minimum well structure elevation shall be set above the jurisdictional water surface to the elevation, as shown on the approved plans and drainage report, and shall be certified by an RLS.
d) Submit completed elevation certificate to City of Tucson Planning & Development Services Department Engineering Division for acceptance. For SAVSARP Well SA-009A, submit final elevation certificate indicating minimum elevation of base flange of well casing. The Floodplain Analysis Summary Report states that the upstream WSEL is 2300.43 and interpolated depth of flood at the well cover of 0.11, and that the well casing shall be 2-ft above any flood level. Regulatory flood level is at minimum 1-foot for AO1 zones. Elevation certificate shall be submitted to show minimum well casing base flange elevation of 2304.43 (using existing grade at well casing 2301.43).
e) Submit a copy of the as-builts, with copies of compaction testing reports, to City of Tucson Planning & Development Services Department upon completion.
2) All conditions of Pima County Regional Flood Control District Floodplain Use Permit No.10-010 approved 2/16/10 shall apply.
3) Additional grading and floodplain review by the City of Tucson Planning & Development Services Department will be required for permits for the future structures or other future phase improvements on the constructed pad. At the time when permits are required for the future control building, submit copy of final elevation certificate with plans and drainage statement.

If you have any questions, call me at 837-4934.

Elizabeth Leibold, P.E., CPM, CFM
Civil Engineer
Engineering Division