Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

Permit Number: T11EL03159
Parcel: 99999999S

Address:
5085 E 29TH ST

Review Status: Completed

Review Details: BILLBOARD - BLDG/ELEC30days

Permit Number - T11EL03159
Review Name: BILLBOARD - BLDG/ELEC30days
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
01/05/2012 GLENN MOYER ADMINISTRATIVE ADMIN REVIEW Denied BRC Comments

Below are comments for the electrical repair plan submittal for COT ID# 318
at 5085 East 29th Street (T11EL03159).

Sheet 1 of 2

No comments.

Sheet 2 of 2

1. Provide the manufacturer and specific model number for the new 122
panel.

2. Clarify if a timer is to be used, and if so provide the manufatrurer and
model number of the timer and indicate the circuit for same in the panel
schedule.

3. Clarify if the 60A rating in the panel schedule is correct (given the
122 panel rating of 30A).

4. In the panel schedule, the stated amperage does not appear to account
for the additional load required for the ballast on each circuit (in the
case of the stated ballast, the input power is 250 watts according to
manufacturers literature, or a minimum entry of 312.5A with the 125% demand
factor included).

5. Correct number of conductors between 122 panel and first junction box in
New Electrical Riser Diagram (for two circuits there should be three
conductors plus ground on this run).

6. Indicate which specific elevation is shown (appears to be east); correct
note as to second elevation having reversed location of service (or delete
note).

7. Add note that no junction boxes or other fixtures where wire connections
are made to be installed other than those shown on plan.

8. Add note that any excess fixtures, conduit, connectors, wiring or
breakers no longer being used to be removed
12/08/2011 LEERAY HANLY BUILDING-COMMERCIAL REVIEW Needs Review
12/08/2011 LEERAY HANLY ELECTRICAL-COMMERCIAL REVIEW Needs Review

Final Status

Task End Date Reviewer's Name Type of Review Description
01/20/2012 GERARDO BONILLA OUT TO CUSTOMER Completed