Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

The login landing page when selecting 'View' is still occurring and is still pending further investigation. 

Permit Number: T11EL02641
Parcel: 13325003A

Address:
8540 E 4TH ST

Review Status: Completed

Review Details: ELECTRICAL

Permit Number - T11EL02641
Review Name: ELECTRICAL
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
10/06/2011 FRODRIG2 ELECTRICAL-RESIDENTIAL REVIEW Approved