Permit Number: T11EL01873
Parcel: 11518032K

Address:
1601 N 15TH AV

Review Status: Completed

Review Details: ELECTRICAL

Permit Number - T11EL01873
Review Name: ELECTRICAL
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
10/21/2011 RAY MAJUTA ELECTRICAL-COMMERCIAL REVIEW Approved T11EL01873, 1601 N 15TH Av
1200 amp Service Upgrade

Electrical denied for following:
1. The plans must shown the location of the following----
800 amp panel,75 kva transformer,the two panels LA and LB,
once owner decides location insert on plan.(Clearances are required to be checked).
2. Provide a drawing showing the entire electrical room.Also
section 110.26.C.2 of the NEC requires panic hardware or equivalent on doors in electrical room.
3. The transformer ground should be #2,per 250.66.
4. The feeder from transformer to Panel LA should be #2 per 250.66.

Ray T Majuta
Elect Pln Ck
PDSD,COT,
10/21/11