Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

Permit Number: T11CM03933
Parcel: 130144360

Review Status: Completed

Review Details: RESUBMITTAL

Permit Number - T11CM03933
Review Name: RESUBMITTAL
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
02/10/2012 ERIC NEWCOMB BUILDING-COMMERCIAL REVIEW Approved
02/13/2012 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Denied 1. Coordinate the civil utilities drawing with the plumbing drawings with respect to the size of the building sewers; 6" on the civil drawings but 4" on the plumbing drawings. Reference: Section 103.2.3, UPC 2006.
2. A separate permit is required for the installation of private manholes for the building sewer system.
02/15/2012 RAY MAJUTA ELECTRICAL-COMMERCIAL REVIEW Approved
02/16/2012 GERRY KOZIOL WWM REVIEW Approved