Permit Number: T11CM03925
Parcel: 11451137D

Review Status: Completed

Review Details: COMMERCIAL - TI

Permit Number - T11CM03925
Review Name: COMMERCIAL - TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
01/17/2012 GBONILL1 WWM REVIEW Needs Review
01/17/2012 GBONILL1 WATER REVIEW Needs Review
12/27/2011 TERRY STEVENS ZONING REVIEW Approved
12/27/2011 LEERAY HANLY MECHANICAL-COMMERCIAL REVIEW Denied PROVIDE MEANS OF EXHAUST FOR RESTROOMS. DETAIL SEQUENCE OF OPERATION FOR ANY EXHAUST FANS TO SHOW EXHAUST WILL ALWAYS EXCEED SUPPLY.
12/27/2011 LEERAY HANLY ELECTRICAL-COMMERCIAL REVIEW Denied ALL OUTLETS IN FOOD PREP AREA TO BE GFCI PROTECTED.
12/27/2011 LOREN MAKUS ENGINEERING REVIEW Approved
12/27/2011 ERIC NEWCOMB BUILDING-COMMERCIAL REVIEW Denied 1. SHEET A-1; CODE ANALYSIS: ACCESSIBILITY CODE IS THE ICC/ANSI A117.1-2003. REVISE.
2. SHEET A-1; CODE ANALYSIS: THE OCCUPANCY GROUP SHOULD NOT BE A B OCCUPANCY. VERIFY AND REVISE.
3. SHEET A-1; CODE ANALYSIS: THE 1:50 (36 OCCUPANTS) SHOULD BE REVISED. USE THE TABLE 1004.1.1.
4. SHEET A-2; BOXED TABLE: THE GRAB BARS LISTED FOR THE 20% COST OF THE TOTAL PROJECT CAN NOT BE USED FOR THIS PROJECT (RESTROOMS ARE BEING REVIEWED UNDER PROJECT NO. T11CMO2872). IF THERE ARE NO OTHER ACCESSIBILITY ISSUES TO BE RESOLVED, REMOVE THE NOTE.
12/27/2011 LEERAY HANLY PLUMBING-COMMERCIAL REVIEW Denied PROVIDE COMPLETE PLUMBING ISOMETRIC FOR ALL NEW DWV AND POTABLE WATER SYSTEMS. DETAIL WHERE CONNECTIONS ARE TO BE MADE TO EXISTING SEWER AND POTABLE SUPPLIES

SPECIFY TYPE AND SIZE OF BACKFLOW PREVENTERS
12/27/2011 DAVE MANN FIRE REVIEW Approved
12/27/2011 ERIC NEWCOMB ADA REVIEW Passed
12/27/2011 BETH GRANT COMMERCIAL IMPACT FEE COMMERCIAL IMPACT FEE PROCESSING Passed