Permit Review Detail
Review Status: Completed
Review Details: COMMERCIAL - TI
Permit Number - T11CM03916
Review Name: COMMERCIAL - TI
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 01/03/2012 | MICHAEL ST. PAUL | ZONING | REVIEW | Approved | |
| 01/03/2012 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Denied | 1. Specify the minimum resistance (R-value) of the duct insulation to be used on this project. Reference: Section 503.2.7, IECC 2006, as amended by the City of Tucson. 2. Complete the specifications by choosing from the multiple-choice phrases in each specification item. Reference: Section 106.3.1, IMC 2006. 3. Provide the installed weight of the rooftop equipment. Reference: Section 106.3.1, IMC 2006. 4. Provide structural calculations to verify that the existing roof is capable of supporting the additional dead load due to the installation of the roof top units. Reference: Section 302.1, IMC 2006. 5. Show the size, routing, and termination of the condensate drains. Reference: Section 307.2, IMC 2006 as amended by the City of Tucson and Section 814.0, UPC 2006. 6. Provide information on the sequence of operation for the restroom exhaust fans to show that all of the air supplied to the restrooms will be exhausted. Reference: Section 403.2.1 (4), IMC 2006. 7. Provide the developed pipe lengths for the natural gas piping. Reference: Section 402.3, IFGC 2006. |
| 01/03/2012 | RAY MAJUTA | ELECTRICAL-COMMERCIAL | REVIEW | Approved | |
| 01/03/2012 | ROBERT SHERRY | WATER | REVIEW | Approved | |
| 03/12/2012 | FRODRIG2 | WWM | REVIEW | Needs Review | |
| 12/23/2011 | ERIC NEWCOMB | BUILDING-COMMERCIAL | REVIEW | Denied | 1. SHEET A5; ELEVATIONS 2: INDICATE ON THE RESTROOM DETAILS THE LOCATIONS AND LENGTHS OF THE GRAB BARS PER ICC/ANSI A117.1-2003, FIGURE 604.5.1. LOCATE THE PAPER DISPENSER PER ICC FIGURE 604.7. |
| 12/23/2011 | RICK MYERS | PLUMBING-COMMERCIAL | REVIEW | Denied | 1. provide the method of sterilization for potable water ststem. reference: 609.0 2006UPC. 2. Reference 413.1 2006 UPC. The water heater thermostat shall not be the sole source of heat control for public use lavatories. 3. Show how the requirements for energy consevation are being met for the potable water system per the 2006 IECC. |
| 12/23/2011 | MARTIN BROWN | FIRE | REVIEW | Approved | |
| 12/23/2011 | ERIC NEWCOMB | ADA | REVIEW | Passed | |
| 12/23/2011 | BETH GRANT | COMMERCIAL IMPACT FEE | COMMERCIAL IMPACT FEE PROCESSING | Passed | |
| 12/29/2011 | PAUL MACHADO | ENGINEERING | REVIEW | Approved |