Permit Number: T11CM03914
Parcel: 12801005H

Review Status: Completed

Review Details: COMMERCIAL - TI

Permit Number - T11CM03914
Review Name: COMMERCIAL - TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
01/13/2012 GERRY KOZIOL WWM REVIEW Approved
01/13/2012 PAUL MACHADO ENGINEERING REVIEW Approved
12/23/2011 MICHAEL ST. PAUL ZONING REVIEW Approved
12/23/2011 RICK MYERS PLUMBING-COMMERCIAL REVIEW Denied 1.reference 413.1 2006 UPC: water heater may not be sole source of heat control for public use lavatory. 2. four inch branch from main will require a full size upper terminal cleanout.
12/23/2011 MARTIN BROWN FIRE REVIEW Approved
12/29/2011 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Denied Clarify the discrepancy between the mechanical plan and detail 1/M.2 with regard to the location of the unit and the structural requirements for the walls and ceiling.
12/29/2011 LEERAY HANLY ELECTRICAL-COMMERCIAL REVIEW Denied 1) PROVIDE AVAILABLE GROUND FAULT CALCULATIONS AND RATING OF EQUIPMENT

2) PROVIDE IECC LIGHTING COMPLIANCE CERTIFICATE
12/29/2011 ROBERT SHERRY WATER REVIEW Approved
12/29/2011 ERIC NEWCOMB BUILDING-COMMERCIAL REVIEW Denied 1. SHEET A2; CEILING PLAN NOTES: NOTE 7 INDICATES TO COORDINATE STRUCTURAL FRAMING HANGERS, ETC., WITH THE STRUCTURAL ENGINEER. NO STRUCTURAL ENGINEER HAS BEEN INCLUDED IN THIS PROJECT. PROVIDE STRUCTURAL CALCULATIONS AND DETAILS (ON THE PLANS) FOR SUPPORT OF THE NEW FANS, AIR HANDLING UNITS, ETC.
2. SHEETS A4 AND A4A; STOREFRONT NOTES: NOTE 6 INDICATES DETAILS TO BE PROVIDED FOR EQUIPMENT SUPPORT BY STRUCTURAL. PROVIDE CALCULATIONS AND DETAILS.
12/29/2011 ERIC NEWCOMB ADA REVIEW Passed
12/29/2011 BETH GRANT COMMERCIAL IMPACT FEE COMMERCIAL IMPACT FEE PROCESSING Passed