Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.

Permit Number: T11CM03897
Parcel: 112062340

Review Status: Completed

Review Details: COMMERCIAL - TI

Permit Number - T11CM03897
Review Name: COMMERCIAL - TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
01/27/2012 CPIERCE1 WWM REVIEW Needs Review
12/22/2011 STEVE SHIELDS ZONING REVIEW Approved
12/22/2011 ROBERT SHERRY WATER REVIEW Approved
12/22/2011 LEERAY HANLY ELECTRICAL-COMMERCIAL REVIEW Approved
12/22/2011 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Approved
12/22/2011 ERIC NEWCOMB BUILDING-COMMERCIAL REVIEW Denied 1. SHEET T1.1: SHOW THE OCCUPANT LOAD ON THIS SHEET.
2. SHEET T1.1: CHANGE THE ACCESSIBILITY CODE DATE TO THE 2003 EDITION.
12/22/2011 JASON GREEN ENGINEERING REVIEW Approved
12/22/2011 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Denied 1. Show that the indirect waste piping complies with the requirements of Section 803.0 with respect to length (i.e. a trap is required for waste pipes greater than five feet in length).
2. Specify the backflow prevention device to be used for each directly-connected appliance. Reference: Section 603.0, UPC 2006.
12/22/2011 MARTIN BROWN FIRE REVIEW Approved
12/22/2011 ERIC NEWCOMB ADA REVIEW Passed
12/22/2011 BETH GRANT COMMERCIAL IMPACT FEE COMMERCIAL IMPACT FEE PROCESSING Passed