Permit Number: T11CM03896
Parcel: 10510010D

Review Status: Completed

Review Details: OTHER

Permit Number - T11CM03896
Review Name: OTHER
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
01/06/2012 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Denied 1. Indirect waste receptors (e.g. hub drains) may not be installed within cabinets; a hub drain does not provide an approved strainer.[Original comment: Provide information to show that the hub drain complies with Sections 411.1 and 804.1, UPC 2006. Detail 1/P00.02 calls for the hub drain to be located in an exposed position but the plumbing plan shows the hub drain located inside a cabinet.]
2. Comment not addressed. Provide information to show how the proposed water heater platform is to be connected to the building structure. Reference: Section 314.5, UPC 2006.
3. Revise the font size used on the drawings to a minimum height of 3/32-inch. Reference: Section 106.1.1, IBC 2006.
01/06/2012 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Denied Revise the font size used on the drawings to a minimum height of 3/32-inch. Reference: Section 106.1.1, IBC 2006.

Final Status

Task End Date Reviewer's Name Type of Review Description
01/17/2012 CPIERCE1 OUT TO CUSTOMER Completed