Permit Review Detail
Review Status: Completed
Review Details: OTHER
Permit Number - T11CM03896
Review Name: OTHER
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 01/06/2012 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Denied | 1. Indirect waste receptors (e.g. hub drains) may not be installed within cabinets; a hub drain does not provide an approved strainer.[Original comment: Provide information to show that the hub drain complies with Sections 411.1 and 804.1, UPC 2006. Detail 1/P00.02 calls for the hub drain to be located in an exposed position but the plumbing plan shows the hub drain located inside a cabinet.] 2. Comment not addressed. Provide information to show how the proposed water heater platform is to be connected to the building structure. Reference: Section 314.5, UPC 2006. 3. Revise the font size used on the drawings to a minimum height of 3/32-inch. Reference: Section 106.1.1, IBC 2006. |
| 01/06/2012 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Denied | Revise the font size used on the drawings to a minimum height of 3/32-inch. Reference: Section 106.1.1, IBC 2006. |
Final Status
| Task End Date | Reviewer's Name | Type of Review | Description |
|---|---|---|---|
| 01/17/2012 | CPIERCE1 | OUT TO CUSTOMER | Completed |