Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.
Permit Review Detail
Review Status: Completed
Review Details: REVISION - - 1ST
Permit Number - T11CM03895
Review Name: REVISION - - 1ST
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 05/14/2012 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Approved | |
| 05/14/2012 | RAY MAJUTA | ELECTRICAL-COMMERCIAL | REVIEW | Denied | T11CM03895 4329 N Oracle RD Revision 1. The electrical service is being relocated to dumpster structure, descrbe how the grounding now will comply with 2005 NEC 250.32. 2. What is the reason for the relocation ? 3. Does relocation change AIC ? 4. Does the new location require physical protection ? Ray T Majuta Elect Plan Review 5/14/12 |
Final Status
| Task End Date | Reviewer's Name | Type of Review | Description |
|---|---|---|---|
| 05/23/2012 | CPIERCE1 | OUT TO CUSTOMER | Completed |