Permit Review Detail
Review Status: Completed
Review Details: RESUBMITTAL
Permit Number - T11CM03895
Review Name: RESUBMITTAL
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 04/02/2012 | STEVE SHIELDS | ZONING | REVIEW | Approved | |
| 04/02/2012 | ERIC NEWCOMB | BUILDING-COMMERCIAL | REVIEW | Approved | |
| 04/02/2012 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Denied | Comment not resolved; sheet P300 still shows four instances of 2" cleanouts (located in lines called out as being 2") serving 3" drains. The note calling for line-sized cleanouts was not evident on the revised drawings (and wouldn't apply in this case anyway). [Second comment: Comment not resolved; sheet P300 still shows 2" cleanouts for 3" drains.] [Original comment: Provide cleanouts sized per Section 708.7, IPC 2006 (e.g. a 3" drain requires a 3" cleanout).] |
| 04/02/2012 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Approved | |
| 04/02/2012 | ROBERT SHERRY | WATER | REVIEW | Denied | Comment not resolved; detail 1/P301 still shows the reduced pressure backflow preventer located inside of the building. [Second comment: Comment not resolved; the reduced pressure backflow assembly is still shown inside of the building and not accessible to Tucson Water.] [Original comment: Reduced pressure backflow prevention assemblies for the building water service are required to be installed in locations accessible to Tucson Water. Reference: Chapter XXVII, Article V, Section 27-72, the Tucson Code, http://cms3.tucsonaz.gov/sites/default/files/water/docs/backflow-ordinance.pdf] |