Permit Number - T11CM03895
Review Name: OTHER
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 03/15/2012 | LEERAY HANLY | BUILDING-COMMERCIAL | REVIEW | Denied | 1. PREVIOUS COMMENT 1: IT DOES NOT APPEAR THERE ARE THE REQUIRED 7 ACCESSIBLE SPACES FOR THE PATIO. VERIFY. NON-FIXED SEATING CAN RESOLVE THIS ISSUE. 2. PREVIOUS COMMENT 2: IT DOES NOT APPEAR THERE ARE THE REQUIRED 17 ACCESSIBLE SPACES FOR THE PATIO + DINING AREAS. VERIFY. NON-FIXED SEATING CAN RESOLVE THIS ISSUE. 3. PREVIOUS COMMENT 3: THE NOTE CONCERNING SOLID GROUTED CMU WAS NOT REMOVED. VERIFY. 4. PREVIOUS COMMENT 5: KEY NOTE 12 NOW REFERENCES 10/A704. SHEET 704 IS NOT INCLUDED IN THIS SET. THE KEY NOTE WAS NOT FOUND ON THE PLAN. 5. PREVIOUS COMMENT 7: DETAIL 10/A704 IS CUT OUTSIDE THE AREA DENOTED "ADA ACCESSIBLE" ON THE PLAN. IS THE COUNTER HEIGHT AT DETAIL 10 STILL 2'-10"? SHEET 704 IS NOT INCLUDED IN THIS SET. 6. PREVIOUS COMMENT 10: ADD A NOTE TO DETAIL 7/S000 INDICATING WHERE THE METAL STUDS ARE USED. LOCATE ON THE FLOOR PLAN WHERE THERE ARE METAL STUDS. 7. PREVIOUS COMMENT 12: ADD A NOTE TO DETAIL 4/S000 TO GROUT SOLID ALL CMU BELOW GRADE. 8. SHEET S100; FOUNDATION PLAN NOTES: NOTE 15 REFERENCES 9/S101 FOR THE TRASH ENCLOSURE PLAN. REVISE THE SHEET NUMBER. 9. PREVIOUS COMMENT 21: THE BOXED NOTE ON DETAIL 1/S201 NOW REFERENCES 17/S202. SHEET S202 IS NOT INCLUDED IN THIS SET. 10. GENERAL: PROVIDE WRITTEN RESPONSES TO ALL REVIEW COMMENTS. |
Final Status
| Task End Date | Reviewer's Name | Type of Review | Description |
|---|---|---|---|
| 04/02/2012 | CPIERCE1 | OUT TO CUSTOMER | Completed |