Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

PRO is currently experiencing an outage. Some documents and records may not be available on PRO momentarily. We apologize for the inconvenience and are working to restore full access.

Permit Number: T11CM03894
Parcel: 12709016A

Review Status: Completed

Review Details: REVISION - - 1ST

Permit Number - T11CM03894
Review Name: REVISION - - 1ST
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
07/03/2012 RAY MAJUTA ELECTRICAL-COMMERCIAL REVIEW Approved
07/09/2012 RONALD BROWN BUILDING-COMMERCIAL REVIEW Denied SHEETS AA and AB
1. The code summary for Tentant B calculates 4 exits required and 5 provided where as the Life Safety Plan shows 4 required exits. Please reconcile.
SHEET AA
2. If Tenant "B" has increased the overall square footage does this not reduce the over square footeage size of Tenant "A" by the same amout? If so, the code summary criteria and requirements would change accordingly. Please recalculate Tenant "A" and reconcile.
SHEET A1.1
3. Please provide a section through the new mezzanine stairs showing all risers, treads, handrails, heights, F.F. elevations and dimensions. Please provide all structural details and calculations as required.
END OF REVIEW
07/10/2012 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Approved

Final Status

Task End Date Reviewer's Name Type of Review Description
07/12/2012 CPIERCE1 APPROVAL SHELF Completed
07/12/2012 CPIERCE1 OUT TO CUSTOMER Completed