Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

PRO is currently experiencing an outage. Some documents and records may not be available on PRO momentarily. We apologize for the inconvenience and are working to restore full access.

Permit Number: T11CM03894
Parcel: 12709016A

Review Status: Completed

Review Details: RESUBMITTAL

Permit Number - T11CM03894
Review Name: RESUBMITTAL
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
01/20/2012 MARTIN BROWN FIRE REVIEW Approved
01/24/2012 RONALD BROWN BUILDING-COMMERCIAL REVIEW Approved
01/26/2012 GERRY KOZIOL WWM REVIEW Denied 1. TENANT "B" WEST SUITE ONLY - FUTURE HOBBY LOBBY - FORMERLY PORTION OF MERVYN'S
2. NEED TO CLARIFY WASTEWATER PLUMBING FIXTURES TO REMAIN WITH ATTENTION TO RESTROOM DRAINS FOR CREDIT EVALUATION
3. WILL NEED 5TH FLOOR WASTEWATER CREDIT EVALUATION FOR EXISTING PLUMBIN FIXTURES TO REAMIN AFTER DRAWING CLARIFICATION AND FOR REMOVAL OF 1-TOILET, 1-LAV & 1-LOUNGE SINK PER DEMO DRAWING D1 DATED 12/16/11
4. NEED TO SHOW LOCATION/METHOD FO CONNECTION TO PUBLIC SEWER
01/31/2012 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Denied Comment not addressed. Note that materials exposed in plenums shall conform to Section 602.2.1, IMC 2006.
01/31/2012 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Denied 1. Comment not addressed. Correct the size of the 2 psig gas piping upstream of RTU-14; 780 CFH at 450 feet requires a 1-1/4" pipe. Reference: Table 402.4(3), IFGC 2006 (Table 12-9, UPC 2006).
2. Comment not addressed. Provide the sizing data (e.g. vent material, total vent height, and offsets) for the flue for the gas-fired unit heater. Reference: Section 511.0, UPC 2006.