Permit Review Detail
Review Status: Completed
Review Details: RESUBMITTAL
Permit Number - T11CM03894
Review Name: RESUBMITTAL
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 01/20/2012 | MARTIN BROWN | FIRE | REVIEW | Approved | |
| 01/24/2012 | RONALD BROWN | BUILDING-COMMERCIAL | REVIEW | Approved | |
| 01/26/2012 | GERRY KOZIOL | WWM | REVIEW | Denied | 1. TENANT "B" WEST SUITE ONLY - FUTURE HOBBY LOBBY - FORMERLY PORTION OF MERVYN'S 2. NEED TO CLARIFY WASTEWATER PLUMBING FIXTURES TO REMAIN WITH ATTENTION TO RESTROOM DRAINS FOR CREDIT EVALUATION 3. WILL NEED 5TH FLOOR WASTEWATER CREDIT EVALUATION FOR EXISTING PLUMBIN FIXTURES TO REAMIN AFTER DRAWING CLARIFICATION AND FOR REMOVAL OF 1-TOILET, 1-LAV & 1-LOUNGE SINK PER DEMO DRAWING D1 DATED 12/16/11 4. NEED TO SHOW LOCATION/METHOD FO CONNECTION TO PUBLIC SEWER |
| 01/31/2012 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Denied | Comment not addressed. Note that materials exposed in plenums shall conform to Section 602.2.1, IMC 2006. |
| 01/31/2012 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Denied | 1. Comment not addressed. Correct the size of the 2 psig gas piping upstream of RTU-14; 780 CFH at 450 feet requires a 1-1/4" pipe. Reference: Table 402.4(3), IFGC 2006 (Table 12-9, UPC 2006). 2. Comment not addressed. Provide the sizing data (e.g. vent material, total vent height, and offsets) for the flue for the gas-fired unit heater. Reference: Section 511.0, UPC 2006. |