Permit Number: T11CM03892
Parcel: 12709016A

Review Status: Completed

Review Details: REVISION - - 1ST

Permit Number - T11CM03892
Review Name: REVISION - - 1ST
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
07/03/2012 RAY MAJUTA ELECTRICAL-COMMERCIAL REVIEW Approved
07/09/2012 RONALD BROWN BUILDING-COMMERCIAL REVIEW Denied SHEETS AA and AB
1. The code summary for Tentant B calculates 4 exits required and 5 provided where as the Life Safety Plan shows 4 required exits. Please reconcile.
SHEET AA
2. If Tenant "B" has increased the overall square footage does this not reduce the over square footeage size of Tenant "A" by the same amout? If so, the code summary criteria and requirements would change accordingly. Please recalculate Tenant "A" and reconcile.
SHEET A1.1
3. Please provide a section through the new mezzanine stairs showing all risers, treads, handrails, heights, F.F. elevations and dimensions. Please provide all structural details and calculations as required.
END OF REVIEW
07/10/2012 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Passed

Final Status

Task End Date Reviewer's Name Type of Review Description
07/12/2012 FERNE RODRIGUEZ OUT TO CUSTOMER Completed