Permit Review Detail
Review Status: Completed
Review Details: REVISION - - 1ST
Permit Number - T11CM03892
Review Name: REVISION - - 1ST
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 07/03/2012 | RAY MAJUTA | ELECTRICAL-COMMERCIAL | REVIEW | Approved | |
| 07/09/2012 | RONALD BROWN | BUILDING-COMMERCIAL | REVIEW | Denied | SHEETS AA and AB 1. The code summary for Tentant B calculates 4 exits required and 5 provided where as the Life Safety Plan shows 4 required exits. Please reconcile. SHEET AA 2. If Tenant "B" has increased the overall square footage does this not reduce the over square footeage size of Tenant "A" by the same amout? If so, the code summary criteria and requirements would change accordingly. Please recalculate Tenant "A" and reconcile. SHEET A1.1 3. Please provide a section through the new mezzanine stairs showing all risers, treads, handrails, heights, F.F. elevations and dimensions. Please provide all structural details and calculations as required. END OF REVIEW |
| 07/10/2012 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Passed |
Final Status
| Task End Date | Reviewer's Name | Type of Review | Description |
|---|---|---|---|
| 07/12/2012 | FERNE RODRIGUEZ | OUT TO CUSTOMER | Completed |