Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

PRO is currently experiencing an outage. Some documents and records may not be available on PRO momentarily. We apologize for the inconvenience and are working to restore full access.

Permit Number: T11CM03892
Parcel: 12709016A

Review Status: Completed

Review Details: RESUBMITTAL

Permit Number - T11CM03892
Review Name: RESUBMITTAL
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
01/20/2012 MARTIN BROWN FIRE REVIEW Approved
01/23/2012 RAY MAJUTA ELECTRICAL-COMMERCIAL REVIEW Approved
01/24/2012 RONALD BROWN BUILDING-COMMERCIAL REVIEW Denied 1. Previous Comments 1 through 7:
In discussions with the building official, Mr. Ron Boose, a building site plan needs to be part of the tenant improvement permit drawing package. The site plan does not have to be a full blown approved development package nor a zoning site plan. It needs to show accessibility, parking, right of way access, location of building on the site, egress and ingress and etc. to provide a proper 2006 IBC code compliance review.
2. Previous Comment 9:
a. Door 14 on sheet SA1 has not been revised for compliance.
END OF REVIEW
01/25/2012 JASON GREEN ENGINEERING REVIEW Denied DATE: January 25, 2012
REVIEWER: Jason Green, CFM
ACTIVITY: T11CM03892 (Building Plan)

SUMMARY: Engineering Division of Planning & Development Services Department has received the building plan (T11CM03892). Engineering Division does not recommend approval of the building plan applications at this time. The following items need to be addressed:


BUILDING PLAN COMMENTS:

1) Engineering could not verify that the building plan was in compliance with a stamped approved Development Plan Package, DP12-0007, for the proposed expansion. Please submit a copy of the stamped approved Development Plan, landscape, and NPPO plans with the next building plan submittal.

2) Engineering will re-review the building plan on the next submittal to insure compliance with the approved and stamped Development Plan Package. Additional comments may be forthcoming.


GENERAL COMMENTS:

Please provide the building plan with a copy of the last approved Development Plan Package. Further comments may be generated upon resubmittal of the building plan review.

For questions or to schedule an appointment I can be reached at 837-4929.
01/26/2012 GERRY KOZIOL WWM REVIEW Denied 1. TENANT "A" EAST SUITE ONLY - FUTURE STEINMART - FORMELY PORTION OF MERVY'S - RECOUNTED ALL WASTEWATER PLUMBING FIXTURES - NEED WASTEWATER 5TH FLOOR CREDIT EVALUATION FOR REMOVAL OF 1- HAND SINK & A-2 FS PER DEMO DRAWINGS D1 DATED 12/16/11
2. NEED TO SHOW LOCATION/METHOD OF CONNECTION TO PUBLIC SEWER
01/31/2012 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Approved
01/31/2012 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Denied 1. Comment not addressed. (Note that flue size is not within the scope of the IMC.) Provide the sizing data (e.g. vent material, total vent height, and offsets) for the flue for the gas-fired unit heater. Reference: Section 511.0, UPC 2006.
2. Comment not addressed on the drawing. Provide cleanouts sized per Section 707.11, UPC 2006 (e.g. the 4" drain located downstream of the east water closet in the women's restroom requires a 4" cleanout).

Final Status

Task End Date Reviewer's Name Type of Review Description
02/03/2012 GERARDO BONILLA OUT TO CUSTOMER Completed
02/02/2012 GERARDO BONILLA REJECT SHELF Completed