Permit Number: T11CM03875
Parcel: 12110005D

Address:
4730 E GRANT RD

Review Status: Completed

Review Details: RESUBMITTAL

Permit Number - T11CM03875
Review Name: RESUBMITTAL
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
02/14/2012 RAY MAJUTA ELECTRICAL-COMMERCIAL REVIEW Denied T11CM03875
4730 E Grant
TI Fitness Center

1. Sheet E-2 Tan Unit #5 has not been circuited in the panel schedule.
2. Sheet E-5, the following circuits are in the panel schedules,cannot locate in the power or lighting plans,

Pnl LA-19,21,23,25,27
Pnl LB- 15,17,19,23,25,35,37,39,41,20,22,24,28,30,32,34
PnlLC- 21,23,26,28,30,
Pnl HA= 15,17,19,23
3. Sheet E-5, under Main Load Summary,what does LCL at 32amp mean ? Where does it come from ?
4. Sheet E-5, shown is a 150 amp feeder and a 175 amp feeder , both feed a combination of 9 AC units, how is this done ?
5. Sheet E-2, what does ciecuit D-12 go to , what does
it do ?
6. Since MSA and MSB both now feed one building, are the grounding systems connected together ?

Ray T Majuta
Elect Pln Review
PDSD, C of Tucv
2/16/12
Ray.majuta@tucsonaz.gov

Pnl LB 15,17,19,23,35,37,39,41,20,22,24,26,28,30,32,34
Pnl LC 21,23,26,28,30,
Pnl HA 15,17,19,21,23,
02/16/2012 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Denied Comment not resolved; the drawing still shows diffusers located within 8'-0" of the center of the fan. [Original comment: The manufacturer calls for the diffusers to be located at least The mechanical ceiling fan shows several HVAC diffusers located within twice the diameter of the large ceiling fans which not recommended by the fan manufacturer. Revise the mechanical design so that the equipment is being installed in accordance with the conditions of its listing and the manufacturer's installation requirements. Reference: Section 304.1, IMC 2006. ]
02/16/2012 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Denied 1. Clarify what constitutes the complete natural gas system. Based on the model numbers for the rooftop A/C units on sheet M1.0, units AC-1A and AC-7 are the only units with gas heat but the plumbing drawing does not show any gas piping being connected to those units. [Original comment: Provide a design for the complete natural gas system (i.e. the AC units as well as the water heater). Include the each connected load, the developed pipe lengths to each load on plans. Reference: Section 402.3, IFGC 2006.]
2. Clarify which water heater is being installed; the specified A.O. Smith model BT-80 has a tank capacity of 74 gallons but the BT-100 has a tank capacity of 98 gallons. Both models have 4" draft hoods which precludes the use of a 3" connector as shown in detail H/P3.0. [Original comment: Show how the vent for the water heater has been sized, including the vent materials, the total vent height, offset dimensions, and the size of the draft hood on the appliance. Reference: Sections 503.6.9 and 504.2.2, IFGC 2006.]
02/16/2012 ROBERT SHERRY WATER REVIEW Approved