Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.
Permit Review Detail
Review Status: Completed
Review Details: COMMERCIAL - TI
Permit Number - T11CM03875
Review Name: COMMERCIAL - TI
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 01/04/2012 | LEERAY HANLY | ELECTRICAL-COMMERCIAL | REVIEW | Denied | 1) PROVIDE CALCULATIONS FOR AVAILABLE FAULT CURRENTS TO JUSTIFY RATINGS OF PANELS. 2) CLARIFY IF PANEL "A" ON ONE LINE IS ACTUALLY PANEL "HA" 3) CLARIFY IF PANELS LA, LB, LC ARE NEW AS NOTED ON PP E2 OR IF THEY ARE EXISTING AS NOTED ON E5. 4) INDICATE ON PLANS THE LOCATION OF 'MSB' SWITCH GEAR & METERING AS WELL AS LANDLORD METERING AND PANEL "LD" 5) PROVIDE 2006 IECC LIGHTING COMPLIANCE INFORMATION. 6) CLARIFY LIGHTING ON PP E1. SOME CIRCUITS ARE NOT IDENTIFIED, SOME REFERENCE SYMBOLS DID NOT REPRODUCE AND NO EMERGENCY LIGHTING IS SHOWN IN ONE OF THE AEROBICS (?) ROOMS. 7) INDICATE CIRCUITING FOR QUAD FLUSH FLOOR OUTLETS AND TREADMILLS PP E2 8) SHOW MECHANICAL CODE COMPLIANCE FOR NEW EXHAUST FANS IN RESTROOM. EG--- SEQUENCE OF OPERATION AS A WALL SWITCH WILL BE INSUFFICIENT TO RELIABLY REMOVE AIR WHEN A/C TURNS ON. 9) PP E4 HAS A DETAIL SHOWING PLUG RECEPTACLES ABOVE THE FINISHED CEILING TO SUPPLY POWER TO CONTROLLER. PLEASE CLARIFY HOW THE FLEXIBLE CORD THROUGHT THE CEILING COMPLIES WITH SECTIONS 400.7 & 400.8 OF THE NEC. |
| 01/04/2012 | ROBERT SHERRY | WATER | REVIEW | Denied | 1. Tucson Water limits a 1-1/2" meter to a maximum demand of 50 GPM. Provide a letter from Tucson Water confirming that the use of a 1-1/2" water meter will be allowed for this project. 2. Provide the size of the reduced pressure backflow prevention assembly serving this building. Reference: Section 106.3.1, IPC 2006. |
| 01/05/2012 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Denied | 1. Provide plans sealed by an Arizona Registrant. Reference: Arizona Revised Statutes 32-125, Board of Technical Registration Rules R4-30-304. 2. Section R4-30-304 of the Rules of the Arizona State Board of Technical Registration, states that a notation shall be placed beneath the seal, either written, typed, or electronically generated, that provides the day, month, and year of the expiration of current registration. (Effective March 8, 2008). 3. Either the Uniform Plumbing Code, 2006 or the International Plumbing Code, 2006, may be used for this activity (if the IPC is selected, then the 2006 International Fuel Gas Code will also be required). The plumbing General Notes on sheet P1.0 refer to the 2007 California Plumbing Code but the Code analysis on sheet TS refers to the 2006 IPC. This review has been made using the 2006 IPC, 2006 IFGC, and the 2006 IECC. 4. Provide plumbing plans for all of the new work, including water isometrics and waste and vent isometrics. Show the location of all required cleanouts on the waste and vent isometrics. Reference: Sections 102.4 and 106.3.1, IPC 2006. 5. Provide a detail of the water heater installation, including the termination point of the excess pressure relief, the size of the expansion tank, any vacuum relief devices, recirculating pump and valves. (Note that the location of the expansion tank in detail F/P3.0 is incorrect.) Reference: Sections 502.1, 503.1, 503.2, 504, 607.2, and 607.3 IPC 2006. 6. If the specified water heater is not supplied with integral heat traps, provide heat traps on the supply and discharge piping. Reference: Section 504.4, IECC 2006. 7. Show how the maximum mixed water temperature is to be limited for the shower. Reference: Sections 424.3, 424.4, and 607.1, IPC 2006. 8. Show how the temperature of the hot water supply to the public lavatories is controlled. Reference: Section 504.3, IECC 2006. 9. Water heaters with inputs of 200,000 BTUH or greater are classified as boilers and require approval from the Arizona Boiler inspector. Reference: Title 20, Chapter 5, Article 4, Arizona Administrative Code. 10. Provide a design for the complete natural gas system (i.e. the AC units as well as the water heater). Include the each connected load, the developed pipe lengths to each load on plans. Reference: Section 402.3, IFGC 2006. 11. Show how the vent for the water heater has been sized, including the vent materials, the total vent height, offset dimensions, and the size of the draft hood on the appliance. Reference: Sections 503.6.9 and 504.2.2, IFGC 2006. |
| 01/05/2012 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Denied | 1. Provide plans sealed by an Arizona Registrant. Reference: Arizona Revised Statutes 32-125, Board of Technical Registration Rules R4-30-304. 2. Section R4-30-304 of the Rules of the Arizona State Board of Technical Registration, states that a notation shall be placed beneath the seal, either written, typed, or electronically generated, that provides the day, month, and year of the expiration of current registration. (Effective March 8, 2008). 3. The International Mechanical Code, 2006 and the International Energy Conservation Code, 2006, are the controlling codes for this activity. The Mechanical General Notes on sheet M1.0 refer to the 2007 California Mechanical Code and to the California Energy Conservation Standards but the Code analysis on sheet TS refers to the 2006 IMC and the 2006 IECC. Screening of the mechanical equipment using the City of Santa Ana Guidelines is not required. This review has been made using the 2006 IMC and the 2006 IECC. 4. Specify the minimum resistance (R-value) of the duct insulation to be used on this project. Reference: Section 503.2.7, IECC 2006, as amended by the City of Tucson. 5. Provide structural details to show how the 12'-0" diameter ceiling fans are being connected to this particular building structure and provide structural calculations to show that the building structure is not being adversely affected. Reference: Section 302.1, IMC 2006. 6. The mechanical ceiling fan shows several HVAC diffusers located within twice the diameter of the large ceiling fans which not recommended by the fan manufacturer. Revise the mechanical design so that the equipment is being installed in accordance with the conditions of its listing and the manufacturer's installation requirements. Reference: Section 304.1, IMC 2006. 7. Show that a separation of at least ten feet exists between air intake openings and exhaust openings. Reference: 401.4.1, IMC 2006. 8. Clarify the sequence of operation for the restroom exhaust fans, EF-1 and EF-2, to verify that all of the air supplied to the restrooms will be exhausted. Reference: Section 403.2.1 (4), IMC 2006. 9. Provide calculations to show that adequate outside air is being provided to each of the different occupancies in the building. Reference: Sections 403.3 and 403.3.2, IMC 2006. |
| 01/19/2012 | GERRY KOZIOL | WWM | REVIEW | Denied | 1. CHUZE FITNESS - TUCSON 1 2. RECOUNTED ALL WASTEWATER PLUMBING FIXTURES - NEED TO CLEARLY IDENTIFY SUITES - PRESENT & FUTURE AND CLEARLY IDENTIFY ALL PLUMBING FIXTURES CONNECTED TO SEWER THAT ARE BEING DEMOLISHED - NOTE: SOME PLUMBING FIXTURES WERE "FOR DISPLAY ONLY & NOT CONNECTED TO SEWER - FORMERLY A KB HOME MODEL SHOWROOM 3. NEED WASTEWATER 5TH FLOOR CREDIT EVALUATION - 740-6602 OR 740-6606 |
| 12/23/2011 | ERIC NEWCOMB | BUILDING-COMMERCIAL | REVIEW | Denied | 1. SHEET TS; CODES: THE CODES LISTED ARE NOT "ARIZONA" SPECIFIC. REMOVE THE ARIZONA REFERENCE. 2. SHEET N1.0; SPECIFICATIONS: THE CITY OF TUCSON REQUIRES ALL LETTERING (UPPER AND LOWER CASE) TO BE A MINIMUM OF 3/32" IN HEIGHT. REVISE. 3. SHEET A2.0; SUBJECT STRUCTURE INFORMATION: IS THIS TYPE IV CONSTRUCTION? VERIFY PER IBC SECTION 602.4. 4. SHEETS A2.0/A2.1/A2.2/A4.2/A4.3: THE CITY OF TUCSON REQUIRES ALL LETTERING (UPPER AND LOWER CASE) TO BE A MINIMUM OF 3/32" IN HEIGHT. REVISE. 5. SHEET A4.3; DETAILS: PROVIDE DETAILS FOR GRAB BARS PER THE ICC/ANSI FIGURES 604.5.1, 604.5.2, AND 604.7. 6. SHEET A4.3; DETAILS: PROVIDE DETAILS FOR THE ACCESSIBLE SHOWERS PER THE ICC/ANSI SECTION 607. 7. GENERAL: INCLUDE THE STRUCTURAL DETAILS (FROM THE CALCULATIONS) ON A FULL SIZE SHEET FOR THE NEW OPENINGS IN THE CMU WALL. 8. GENERAL: PROVIDE WRITTEN RESPONSES FOR ALL REVIEW COMMENTS. |
| 12/23/2011 | FRODRIG2 | FIRE | REVIEW | Needs Review |