Permit Number: T11CM03828
Parcel: 13220007G

Review Status: Completed

Review Details: REVISION - - 1ST

Permit Number - T11CM03828
Review Name: REVISION - - 1ST
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
01/18/2012 RAY MAJUTA ELECTRICAL-COMMERCIAL REVIEW Denied Electrical comments: Plans have been review and denied for the following ,

1. Tapping the existing 4000 amp MSB with 3 sets of
3#300mcm,#3 grd violates the intended use, Listing and Approval of the MSB.
2. Setting the 800 amp Mian Disconnect (mounted to the back of the MSB) violates the Listing and Approval of the MSB.
3. Once the MSB is changed or modified in any way the MSB must be re evaluated. RE Listed and Approved by an OSHA approved Testing Lab.

Ray Majuta
PDSD,City of Tucson,
Elect Pln Review,
1/18/12

Final Status

Task End Date Reviewer's Name Type of Review Description
01/24/2012 CPIERCE1 OUT TO CUSTOMER Completed