Permit Review Detail
Review Status: Completed
Review Details: REVISION - - 1ST
Permit Number - T11CM03828
Review Name: REVISION - - 1ST
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 01/18/2012 | RAY MAJUTA | ELECTRICAL-COMMERCIAL | REVIEW | Denied | Electrical comments: Plans have been review and denied for the following , 1. Tapping the existing 4000 amp MSB with 3 sets of 3#300mcm,#3 grd violates the intended use, Listing and Approval of the MSB. 2. Setting the 800 amp Mian Disconnect (mounted to the back of the MSB) violates the Listing and Approval of the MSB. 3. Once the MSB is changed or modified in any way the MSB must be re evaluated. RE Listed and Approved by an OSHA approved Testing Lab. Ray Majuta PDSD,City of Tucson, Elect Pln Review, 1/18/12 |
Final Status
| Task End Date | Reviewer's Name | Type of Review | Description |
|---|---|---|---|
| 01/24/2012 | CPIERCE1 | OUT TO CUSTOMER | Completed |