Permit Number: T11CM03795
Parcel: 13308017A

Review Status: Completed

Review Details: RESIDENTIAL - BLDG/WWM

Permit Number - T11CM03795
Review Name: RESIDENTIAL - BLDG/WWM
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
01/03/2012 KEN VAN KARSEN BUILDING-RESIDENTIAL REVIEW Denied PLAN REVIEW COMMENTS

Plan review for the above referenced structure has been completed. This letter reflects comments to be addressed. In order to facilitate a shorter back check time, we request that you please provide revised plans and calculations, highlighting any changes, along with a written response to each of the notated items indicating action taken.

SCOPE OF REVIEW:
The scope of this plan review covers architectural, plumbing, mechanical, energy conservation and electrical. All code references are to the 2006 International Residential Code, 2006 International Energy Conservation Code, and Arizona State amendments to the 2006 Uniform Plumbing Code. All features were checked only to the extent allowed by the submittals provided. All portions of this project are assumed to meet or will meet other departmental requirements, conditions and concerns before permit approval.

GENERAL REQUIREMENTS:
Show corrections and revisions on original tracings or a finished reproducible set. Return two sets along with a set of the first submission for reference. Pen or pencil corrections on final prints will not be acceptable. To avoid delays, ensure that all corrections have been made, are complete, and have been coordinated on all applicable detail and notate sheets. (Do not cloud the changes made for comment revisions). Incorporate changes on originals and provide two copied sets for review.

All engineers and architects involved in the design of the structure are to seal the related sheets of plans, details and calculations in accordance with the rules of the State Board of Technical Registration.

GENERAL NOTES:

" Provide legible notation (minimum 3/32" lettering). Clarify lettering on sheet #A101, A102 and S101.

FOUNDATION PLANS:

1. Show a foundation for accommodating the stairway load on sheet A201, R301.5.
2. The footing projection shall not exceed the thickness, R403.1.1. Revise the details on sheet #A201
3. Show all foundation hold-downs for alternate brace wall panels at panel corner points, R403.1.6. Relocate the two hold-down symbols on sheet #A201 shown at window opens.
4. The PAHD series shown on A201 has been discontinued. Revise the Braced Wall Panel notation with a device and an installation method that provides the required 1800 LBS uplift capacity, R602.10.6. Select a series for stem wall installation.

SECTIONS - DETAILS:

1. Revise the exterior Sonotube detail references shown on the plan sheet A201 as 10/S101 rather than 1/A201.
2. Show untreated wood framing with a minimum 8" clearance above the ground, or show floor joist as pressure treated, R319.1 item 2.
3. Specify stair width (min 36", R311.5.1), rise and run (min. 10" tread depth, 7 ¾" max. riser height, R311.5.3), landing width (R311.5.4), handrail height (R311.5.6.1), guardrail height (R312.1) and intermediate rail spacing (R312.2). Maximum vertical rise is 12' between floors or landings, R311.5.4.
4. Show the location of roof vents, R806.
5. Show a minimum 3' chimney height above the point where it passes through the roof, R1003.9.
6. Identify factory-built fireplace compliance with R1004 and chimney compliance with R1005.

MECHANICAL PLANS:

1. Provide heating facilities in all habitable rooms, R303.8. Provide a means of heating the Office, and identify a rating for the fireplace for sufficiently heating the Great Room.

ELECTRICAL PLANS:

1. A wall switch for illuminating stairs must be provided at each floor level of stairways with six or more risers, R303.6.1.
2. Provide a panel schedule showing panel size, circuit numbers, ampacity, wire size and general description, E3304.11 & E3606.2.
3. Show the location of the panel on the Electrical Plan, E3501.6.2 & E3605.8.
4. Designate the circuit number at the location of each light fixture, receptacle, appliance and equipment disconnect switch, E3603.5.
5.

OUTDOOR LIGHTING CODE

1. Show the proposed fixture as full cut-off FCO style, or provide an Outdoor Lighting Calculation including all exterior fixtures on the property for determining exterior lighting limits.

If you have any questions please contact:
Ken Van Karsen
(520) 837-4912
City of Tucson Residential Plan Review
01/05/2012 GBONILL1 WWM REVIEW Passed

Final Status