Review Date Reviewer's Name Type of Review Description Status Comments
12/13/2011 STEVE SHIELDS ZONING REVIEW Approved
12/13/2011 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Approved
12/13/2011 RONALD BROWN ADA REVIEW Passed
12/13/2011 ROBERT SHERRY WATER REVIEW Approved
12/13/2011 RONALD BROWN BUILDING-COMMERCIAL REVIEW Needs Review
12/13/2011 PAUL MACHADO ENGINEERING REVIEW Approved
12/13/2011 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Approved
12/13/2011 MARTIN BROWN FIRE REVIEW Approved
12/13/2011 BETH GRANT COMMERCIAL IMPACT FEE COMMERCIAL IMPACT FEE PROCESSING Passed
12/14/2011 GERRY KOZIOL WWM REVIEW Approved
12/14/2011 RAY MAJUTA ELECTRICAL-COMMERCIAL REVIEW Approved T11CM03793
4649 E 22nd ST
TI Remodel Face Lift Ext


Electrical notes:

1. Provide 2006 IECC Budget Lighting Compliance Report, ComCheck ok.
2. Provide a grounding detail for new service per 2005 NEC 250 and size.
3. Cannot locate service receptacles for HVAC equipment required by 2005 NEC 210.63.
4. Cannot locate circuit B-4, for receptacles in warehouse ?


Ray T Majuta
Electrical Plan Review
PDSD, C of T