Permit Number: T11CM03788
Parcel: 12417168C

Review Status: Completed

Review Details: COMMERCIAL - TI

Permit Number - T11CM03788
Review Name: COMMERCIAL - TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
12/13/2011 STEVE SHIELDS ZONING REVIEW Approved
12/13/2011 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Approved
12/13/2011 RAY MAJUTA ELECTRICAL-COMMERCIAL REVIEW Denied T11CM03788


Need Panel loads and time clock on bath room exhaust fan due to supply air, per Mechanical.

Ray T Majuta
12/13/11
12/13/2011 ROBERT SHERRY WATER REVIEW Approved
12/13/2011 RONALD BROWN BUILDING-COMMERCIAL REVIEW Denied 1. Provide accessible reception counter, 36" high x 36" wide.
2. Sink counter to be 2'-10" high
3. 3' wide corridor does not comply with ICC/ANSI 117.1, Section 404.3.2.1.
4. Show entire office/warehouse space, include warehouse.
5. Finish building code analysis including occupant load calculation
6. Need drinking water dispenser/s
7. Call out 1 hour partition on the floor plan and insure all doors in partition are rated to the partition fire rating as noted.
END OF COMMENTS
12/13/2011 PAUL MACHADO ENGINEERING REVIEW Approved
12/13/2011 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Approved
12/13/2011 MARTIN BROWN FIRE REVIEW Approved
12/13/2011 RONALD BROWN ADA REVIEW Passed
12/13/2011 BETH GRANT COMMERCIAL IMPACT FEE COMMERCIAL IMPACT FEE PROCESSING Passed
12/14/2011 FRODRIG2 WWM REVIEW Needs Review