Permit Review Detail
Review Status: Completed
Review Details: COMMERCIAL - TI
Permit Number - T11CM03788
Review Name: COMMERCIAL - TI
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 12/13/2011 | STEVE SHIELDS | ZONING | REVIEW | Approved | |
| 12/13/2011 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Approved | |
| 12/13/2011 | RAY MAJUTA | ELECTRICAL-COMMERCIAL | REVIEW | Denied | T11CM03788 Need Panel loads and time clock on bath room exhaust fan due to supply air, per Mechanical. Ray T Majuta 12/13/11 |
| 12/13/2011 | ROBERT SHERRY | WATER | REVIEW | Approved | |
| 12/13/2011 | RONALD BROWN | BUILDING-COMMERCIAL | REVIEW | Denied | 1. Provide accessible reception counter, 36" high x 36" wide. 2. Sink counter to be 2'-10" high 3. 3' wide corridor does not comply with ICC/ANSI 117.1, Section 404.3.2.1. 4. Show entire office/warehouse space, include warehouse. 5. Finish building code analysis including occupant load calculation 6. Need drinking water dispenser/s 7. Call out 1 hour partition on the floor plan and insure all doors in partition are rated to the partition fire rating as noted. END OF COMMENTS |
| 12/13/2011 | PAUL MACHADO | ENGINEERING | REVIEW | Approved | |
| 12/13/2011 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Approved | |
| 12/13/2011 | MARTIN BROWN | FIRE | REVIEW | Approved | |
| 12/13/2011 | RONALD BROWN | ADA | REVIEW | Passed | |
| 12/13/2011 | BETH GRANT | COMMERCIAL IMPACT FEE | COMMERCIAL IMPACT FEE PROCESSING | Passed | |
| 12/14/2011 | FRODRIG2 | WWM | REVIEW | Needs Review |