| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 12/06/2011 | DAVE MANN | FIRE | REVIEW | Approved | |
| 12/22/2011 | LEERAY HANLY | ELECTRICAL-COMMERCIAL | REVIEW | Denied | PLEASE REFERENCE IN THE PLANS THAT YOU INTEND TO COMPLY WITH THE 2008 NEC. THE 2005 NEC DOES NOT ALLOW FOR THE SUM OF THE AMPERE RATINGS OF THE OVERCURRENT DEVICES SUPPLYING POWER TO A BUSBAR TO EXCEED THE RATING OF THAT BUSBAR. [NEC 690.64] 2) YOU MAY NOT USE A 100 A BACKFED BREAKER FROM THE PV SYSTEM ON A 400 A BUSBAR UNLESS YOU DERATE THE MAIN OVERCURRENT DEVICE WHICH IS ALSO FEEDING THAT BUSBAR. THE SUM OF THE OVERCURRENT DEVICES MAY NOT EXCEED 480 A [NEC 690.64] |
| 12/22/2011 | LEERAY HANLY | BUILDING-COMMERCIAL | REVIEW | Denied | 1) PLEASE CLARIFY IN PLAN SET HOW YOU ARE GOING TO INSTALL A 2x6 RAFTER INTO A 2x4 SPACE [IBC 106] 2) PLEASE PROVIDE STRUCTURAL CALCULATIONS THAT ACCOUNT FOR THE NECESSITY OF NOTCHING 2" OUT OF A 2x6 IN ORDER TO COMPLY WITH ITEM 1 ABOVE. [IBC 106]. AS AN ALTERNATIVE YOU MAY CONSIDER USING HANGERS TO SUPPORT THE 2x6 RAFTERS...IF YOU DO THEN PROVIDE A DETAIL IN THE PLAN SET |