Permit Number: T11CM03721
Parcel: 131010460

Address:
5028 E 22ND ST

Review Status: Completed

Review Details: COMMERCIAL - BLDG/FIRE/ZONING/ENG

Permit Number - T11CM03721
Review Name: COMMERCIAL - BLDG/FIRE/ZONING/ENG
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
12/06/2011 DAVE MANN FIRE REVIEW Approved
12/22/2011 LEERAY HANLY ELECTRICAL-COMMERCIAL REVIEW Denied PLEASE REFERENCE IN THE PLANS THAT YOU INTEND TO COMPLY WITH THE 2008 NEC. THE 2005 NEC DOES NOT ALLOW FOR THE SUM OF THE AMPERE RATINGS OF THE OVERCURRENT DEVICES SUPPLYING POWER TO A BUSBAR TO EXCEED THE RATING OF THAT BUSBAR. [NEC 690.64]

2) YOU MAY NOT USE A 100 A BACKFED BREAKER FROM THE PV SYSTEM ON A 400 A BUSBAR UNLESS YOU DERATE THE MAIN OVERCURRENT DEVICE WHICH IS ALSO FEEDING THAT BUSBAR. THE SUM OF THE OVERCURRENT DEVICES MAY NOT EXCEED 480 A [NEC 690.64]
12/22/2011 LEERAY HANLY BUILDING-COMMERCIAL REVIEW Denied 1) PLEASE CLARIFY IN PLAN SET HOW YOU ARE GOING TO INSTALL A 2x6 RAFTER INTO A 2x4 SPACE [IBC 106]

2) PLEASE PROVIDE STRUCTURAL CALCULATIONS THAT ACCOUNT FOR THE NECESSITY OF NOTCHING 2" OUT OF A 2x6 IN ORDER TO COMPLY WITH ITEM 1 ABOVE. [IBC 106].

AS AN ALTERNATIVE YOU MAY CONSIDER USING HANGERS TO SUPPORT THE 2x6 RAFTERS...IF YOU DO THEN PROVIDE A DETAIL IN THE PLAN SET

Final Status

Task End Date Reviewer's Name Type of Review Description
01/04/2012 GERARDO BONILLA OUT TO CUSTOMER Completed
01/04/2012 SUE REEVES REJECT SHELF Completed