Permit Number: T11CM03707
Parcel: 110120960

Address:
5301 E GRANT RD

Review Status: Completed

Review Details: REVISION - - 3RD

Permit Number - T11CM03707
Review Name: REVISION - - 3RD
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
02/12/2013 RONALD BROWN BUILDING-COMMERCIAL REVIEW Approved
02/13/2013 KEN BROUILLETTE FIRE REVIEW Approv-Cond 1. All fire rated or smoke barriers walls shall be identified in the field with markings.
2. Fire/Smoke Dampers shall be labeled and have access panels. They shall be connected to fire alarm system. Permits are required for modification to the fire alarm system.
3. Any fire sprinkler work will require additional permits.
4. The fire department key box shall be updated with new access cards for readers if necessary.
02/13/2013 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Approved
02/13/2013 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Approved
02/27/2013 RAY MAJUTA ELECTRICAL-COMMERCIAL REVIEW Approved

Final Status

Task End Date Reviewer's Name Type of Review Description
03/06/2013 CPIERCE1 APPROVAL SHELF Completed
03/06/2013 FERNE RODRIGUEZ OUT TO CUSTOMER Completed